ACCESSING SERVICE MODE FOR GAS VALVE ADJUSTMENT
MENU
Switched Live Control
Burner Stabilisation
HeatingHot Water
ACTUALTARGET
75°75°
ACTUALTARGET
75°75°
Demand OnNo Demand
100%8°
Menu
Status Settings
Configuration
Service
Access Level
Maximum Rate
Target Fan Speed
Actual Fan Speed
Time Remaining
Flow Temperature
Return Temperature
Flame Current
6800 rpm
6800 rpm
10 Minutes
75°c
60°c
5.7µA
MIN RATE
Minimum Rate
Target Fan Speed
Actual Fan Speed
Time Remaining
Flow Temperature
Return Temperature
Flame Current
6800 rpm
6800 rpm
10 Minutes
75°c
60°c
5.7µA
MAX RATE
To set the boiler to run at
Maximum Rate for 10 Minutes
press Maximum Rate
The boiler will run at Maximum Rate for
10 minutes unless the system load is
insufficent
The boiler will automatically move back
to normal operation after 10 minutes
To move directly to Minimum Rate
press MIN RATE
The boiler will run at Minimum Rate for
10 minutes unless the system load is
insufficent
The boiler will automatically move back
to normal operation after 10 minutes
To move directly to Maximum Rate
press MAX RATE
To set the boiler to run at
Minimum Rate for 10 Minutes
press Minimum Rate
Press MENU
Press Service