2.3. Supervision
Supervision time is the time that the system waits to receive a check-in signal or a
violation signal.
The X-Series system has two settings:
- 3 hours
- 24 hours
Each device can be set to send a check-in signal every 90 minutes or 12 hours.
This means that if the system is set to a supervision time of “3 hours” and each device
is set to “90 minutes”, the device will send two check-in signals within the “3 hours”.
The system must receive one signal within the supervision time.
To set the X-Series panel’s supervision time you must program it into Location 260,
Sub-location 4.