EasyManuals Logo

Inficon Vortex Dual User Manual

Inficon Vortex Dual
17 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
17
Vortex Dual Operating Manual
English
Table 7-1 EPA Requirements
*mm Hg absolute
The EPA requires that service technicians certify the acquired recovery
equipment to the appropriate EPA Regional Office, and that it is in compliance
with the applicable laws established by the Clean Air Act. Forms are available
from the Regional Office of the EPA.
Questions about the EPA requirements can be answered by contacting the
Ozone Protection Hotline, toll free, at +1.800.296.1996.
TYPE OF APPLIANCE
REQUIRED
INCHES OF HG
VACUUM
HCFC-22 appliance generally containing less than 200
pounds of refrigerant
0
HCFC-22 appliance generally containing 200 pounds or
more or refrigerant
10
Other high pressure appliance generally containing less
than 200 pounds of refrigerant
10
Other high pressure appliance generally containing 200
pounds or more of refrigerant
15
Very high pressure appliance (CFC-13, -503) 0
Low Pressure appliance (CFC-11, HCFC-123) 25*

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inficon Vortex Dual and is the answer not in the manual?

Inficon Vortex Dual Specifications

General IconGeneral
BrandInficon
ModelVortex Dual
CategoryTest Equipment
LanguageEnglish

Related product manuals