Interflex Datensysteme GmbH 2/7
3.1 Shielded Cables
To guarantee trouble-free operation, we recommend the use of shielded cables.
Operation, however, is also possible with unshielded cables. Data transfer problems must be examined on a
case-by-case basis. Where necessary, a shielded cable must be used for the corresponding devices.
The design frame is protected by a transparent foil. Please remove this foil prior to
installation.
3.2 Cables and Cable Types
No.
Max. Length Cable Cores
1 BUS cable from controller to terminal (slave) installed furthest away 1,200 m 4 x 2 x 0.6 mm²
1a Branch cable from bus to installation site of terminal (slave) 100 m 4 x 2 x 0.6 mm²
2 110/ 230 V mains cable to transformer or DC power supply unit
2a Low voltage cable to terminal board (3) 4 x 2 x 0.6 mm²
We recommend:
installing a separate, fuse-protected circuit.
supplying operating voltage via a separate cable (2a) to avoid interference.
keeping a minimum distance of 30 cm between the slave terminal and other systems with RFID readers.
keeping a distance of 10 cm between connecting cables and power lines.
3.3 Open / Close Housing
The back panel of the housing (6) and the housing cover (8) are held together with internal catches and
secured with a mortise lock (3).
1 IF-812/IF-815 terminal (slave) 5 Terminal strip board
2 Tool for opening the housing of the IF-812/IF-815
terminal, order no. 50-10137
6 Back panel of housing
3 Mortise lock 7 Connecting cable
4 Latch hooks 8 Housing cover