Interklima Dx Cassette Units
II-IO CCV1 R410A / Rotary / Scroll
46
The COOL mode SLEEP profile is as follow:
The HEAT mode SLEEP profile is as follows:
2.13. AUTO FAN SPEED
a. In COOL mode, if Tr<Ts+2
o
C, indoor fan runs at low speed.
If Ts+2
o
C≤Tr<Ts+3
o
C, indoor fan runs at medium speed.
If Tr≥Ts+3
o
C, indoor fan runs at high speed.
b. In COOL mode, the fan speed cannot change until it has run at
this speed over 30 seconds.
c. In HEAT mode, if Tr≤Ts-1
o
C, indoor fan runs at low speed.
If Ts-3
o
C≤Tr<Ts-1
o
C, indoor fan runs at medium speed.
If Tr<Ts-3∞C, indoor fan runs at high speed.
d. In HEAT mode, the fan speed cannot change until it has run
at this speed over 30 seconds.
2.14. LOUVER
a. When the unit is connection to power supply, the louver will
swing 100 degrees to close condition.
b. When the unit is turned on, the louver will swing 87 degrees
from close condition to set mode.
c. When the unit is turned off, the louver will swing 100 degrees
back to close condition.
d. At swing mode, louver swings between 59-87 degrees range
and can be set within.
2.15. BUZZER
If a command is received by the air conditioner, the system will
respond with a beep.
2.16. AUTO RESTART
The system uses non-volatile memory to save the present
operation parameters when system is turned off or in case of
system failure or cessation of power supply. Operation
parameters are mode, set temperature, swing, and the fan speed.
When power supply resumes or the system is switched on again,
the same operations as previously set will function.
2.17. RESET BUTTON
a. On the unit front panel next to the LED lights is the reset
button. Press it once and unit will operate according to auto
mode.
b. If the unit is on/off, pressing the button will turn the unit off/on;
if the timer function is activated, pressing the button will
cancel the timer function.
2.18. DRAIN PUMP
a. In cool or dehumidify mode, the drain pump will be turned on
when compressor is on. The drain pump delays 5 minutes to
be turned off after the float switch is closed. When the mode
is changed, the drain pump will remain on for 5 minutes.
b. In any mode (including unit turned off). The drain pump will be
turned on, after the float switch has been opened for 5
seconds. If the float switch has been opened for 5 minutes
continuously, the compressor and the outdoor unit will be
turned off. If the float switch has been opened for 10 minutes
continuously, the system will alarm with beep, pressing the
reset button or any remote handset button will stop the alarm.
The indoor unit will remain on.