EasyManua.ls Logo

Interlogix ATS4500A-IP-LM - Page 32

Interlogix ATS4500A-IP-LM
376 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 2: Installation
26 Advisor Advanced ATSx500A(-IP) Installation and Programming Manual
Zone state
EOL
Connection
details [1]
Measure [2]
Short
Masking
Normal
Alarm
Fault
Open
3K74
(Item 4)
R (kΩ)
<1.25
1.25–
2.45
2.45–
4.99
4.99–
9.98
—
>9.98
RA=3.74 kΩ, RT=1.87 kΩ,
RF=1.87 kΩ
U (V)
<2.90
2.90–
4.80
4.80–
7.10
7.10–
9.40
—
>9.40
3K3
(Item 4)
R (kΩ)
<1.10
1.10–
2.20
2.20–
4.40
4.40–
8.80
—
>8.80
RA=3.3 kΩ, RT=1.65 kΩ,
RF=1.65 kΩ
U (V)
<2.60
2.60–
4.40
4.40–
6.70
6.70–
9.00
—
>9.00
2K
(Item 4)
R (kΩ)
<0.67
0.67–
1.33
1.33–
2.67
2.67–
5.33
—
>5.33
RA=2 kΩ, RT=1 kΩ,
RF=1 kΩ
U (V)
<1.70
1.70–
3.00
3.00–
5.00
5.00–
7.30
—
>7.30
1K5
(Item 4)
R (kΩ)
<0.50
0.50–
1.00
1.00–
2.00
2.00–
4.00
—
>4.00
RA=1.5 kΩ, RT=0.75 kΩ,
RF=0.75 kΩ
U (V)
<1.30
1.30–
2.40
2.40–
4.10
4.10–
6.30
—
>6.30
2K2+4K7
(Item 3)
R (kΩ)
<3.60
—
3.60–
5.60
5.60–
8.20
—
>8.20
RA=2.2 kΩ, RT=4.7 kΩ
U (V)
<6.00
—
6.00–
7.50
7.50–
8.80
>8.80
1K
(Item 7)
R (kΩ)
<0.51
4.52–
40.00
0.51–
1.52
1.52–
2.94
2.94–
4.52
>40.00
RA=1 kΩ, RT=1 kΩ,
RF=12 kΩ
U (V)
<1.35
6.24–
12.33
1.35–
3.36
3.36–
5.29
5.29–
6.74
>12.33
8K2
(Item 5)
R (kΩ)
<1.50
—
1.50–
5.84
5.84–
14.25
—
>14.25
RA=8.2 kΩ, RT=8.2 kΩ
U (V)
<3.33
—
3.33–
7.52
7.52–
10.33
—
>10.33
8K2
(Item 6)
R (kΩ)
<1.50
14.25–
45.00
1.50–
5.84
5.84–
10.07
10.07–
14.25
>45.00
RA=8.2 kΩ, RT=8.2 kΩ,
RF=8.2 kΩ
U (V)
<3.33
10.33–
12.48
3.33–
7.52
7.52–
9.37
9.37–
10.33
>12.48
[1] Refer to Figure 19 on page 27.
[2] Zone resistance R (kΩ), zone voltage U (V).
— The state is not available

Table of Contents