INSTALLATION INSTRUCTIONS
Description:
The passive infrared sensors work by detecting the difference between heat emitted from the human body in motion and the
background space. The sensor switch can turn a load ON and hold it as long as the sensor detects occupancy. After no motion is
detected for the set time delay, the load turns OFF automatically. The sensor switch has one relay (equal to single pole switch), it
also includes Ambient Light Level Sensor.
Coverage Area:
The coverage range of the sensor switch is specified and illustrated in Figure 1. Large objects and some transparent barriers like
glass windows will obstruct the sensor’s view and prevent detection, causing the light to turn off even though someone is still in the
detection area.
LOCATION/MOUNTING
Since this device responds to temperature changes, care should be taken when mounting the device.
DO NOT mount directly above a heat source, in a location where hot or cold drafts will blow directly on the sensor, or where
unintended motion will be within sensor’s field-of-view.
INSTALLATION
1. Connect lead wires as shown in WIRING DIAGRAM (see Figure 2): Black lead to Line (Hot), Red lead to Load
wire, White Lead to Neutral wire, Green lead to Ground.
2. Gently position wires in wall box, attach sensor switch to the box.
3. Mount device “TOP” up.
4. Restore power at circuit breaker or fuse, wait one minute.
5. Remove the small cover plate. (Illustrated as Figure 3.)
6. Locate the adjustment knobs on the control panel to perform test and adjustments.
(Illustrated as Figure 4.)
7. Replace the small cover plate after testing and adjusting.
8. Attach the wallplate.
NOTE: If twist on wire connector is provided, use to join one supply conductor with one 16 AWG device control lead.
ADJUSTMENT
Time Delay Knob
Default position: 15 Seconds (Test mode)
Adjustable: from 15 Seconds to 30 Minutes (clockwise)
Sensor Sensitivity Range Knob
Default position: Center at 65%
Adjustable: 30% (Position 1) to 100% (Position 4)
Note: Turn clockwise for larger rooms. Turn counter clockwise to avoid false alerts in smaller rooms or near
doorway or heat source.
Ambient Light Level Knob: Default position: Daylight (100% at position 4)
Adjustable: Daylight to 30 Lux (Counter clockwise)
OPERATION
Band Switch
Push-button:
As illustrated in Figure 5, the Load stays OFF when the button is pushed in and locked. (switched OFF) As illustrated in Figure 6,
the Load turns ON after the button is pressed and released. The sensor switch stays at the AUTO Mode until the button is pressed
OFF next time.
Occupancy
Sensor Switch
MODEL: IOS-DSIF/IOS-DPBIF
Figure 3
Figure 4
Figure 5
IOS-DSIF
IOS-DPBIF
Ratings:
Incandescent / Tungsten: 500W-120VAC
Fluorescent / Ballast: 500VA-120VAC
Motor: 1/8HP-120VAC
Time Delay: 15 Sec to 30 Min
Light Level: 30 Lux--Daylight
Operation Temperature: 32˚F--131˚F / 0-55˚C
No minimum Load required.
Figure 1
Maximum: 980 sq.ft.
18'
18'
Top View
9'
9'
15'
30'
5'
4'
Side View
150˚ Field of View
Wiring Diagram
Neutral
White
Hot
Black
Ground
Green
Load
Red
Neutral(White)
LOAD
Neutral
White
Hot
Black
Ground
Green
Load
Red
LOAD
Neutral(White)
Figure 2
Press
OFF
(Lock)
Press and release
AUTO
Figure 6
IOS-DSIF
IOS-DPBIF
Risk of Fire, Electrical Shock or Personal Injury
Turn OFF power at circuit breaker or fuse and test that the power is OFF before wiring.
To be installed and/or used in accordance with appropriate electrical codes and regulations.
If you are not sure about any part of these instructions, consult a qualified electrician.
Use this device only with copper or copper clad wire.
INDOOR USE ONLY
WARNING
Mode Position Description
OFF LEFT Circuit is permanently opened (switched off)
AUTO Center Occupancy Mode:
Automatic ON when occupancy is detected.
Automatic OFF after the set time delay.
ON RIGHT Load stays ON always.
Question and Answer IconNeed help?

Do you have a question about the Intermatic IOS-DSIF and is the answer not in the manual?

Intermatic IOS-DSIF Specifications

General IconGeneral
Load Rating (LED)150W
Load Rating (CFL)150W
MountingIn-Wall
Adjustable SensitivityYes
Neutral Wire RequiredYes
Voltage120-277V AC
Detection Range30 ft.
Time DelayAdjustable (30 seconds to 30 minutes)
Operating Temperature32°F to 104°F (0°C to 40°C)
Coverage Area900 sq ft

Summary

Installation Instructions

Warning

Critical safety warnings and precautions before installation.

Description

Explains how the passive infrared sensors detect heat differences for occupancy.

Coverage Area

Details the sensor's detection range and factors affecting it.

Location and Mounting

Guidance on optimal device placement to prevent false detection.

Installation Steps

Step-by-step instructions for wiring and mounting the sensor switch.

Adjustments

Covers Time Delay, Sensitivity Range, and Ambient Light Level controls.

Operation Modes

Describes the function of the Band Switch modes: OFF, AUTO, and ON.

Troubleshooting

Initial Run

Describes the first power-up sequence and initial behavior.

Load Flashing Frequently

Addresses a specific troubleshooting issue where the load flashes.

Load Not Turning On

Troubleshooting for when the load does not activate with motion.

Load Not Turning Off

Troubleshooting steps for when the load fails to turn off.

Unintended Load Activation

Troubleshooting for when the load turns on unexpectedly.