Check if:
INTERSAN MANUFACTURING COMPANY
1748 W. Fillmore St. - Phoenix, Arizona 85007 - Tel 602.254.3101 - Fax 602.254.1776 - www.IntersanUS.com
NOTE: THIS INFORMATION IS SUBJECT TO CHANGE WITHOUT FORMAL NOTICE REV1.2
- 2 -
PROBLEM 2: INSUFFICIENT or NO WATER FLOW WITH CLICKING SOUND
1. Check Sensor Shipping Covers
1. Ball valves and angle stops are in the on position.
2. Stop-valve strainer screens and strainer screens at the entry of the solenoid valves assembly
are clean and debris free.
3. Supply lines are clean and pressure requirements are within the parameters.
4. Thermostatic mixing valve has the correct supply to the hot and cold inlets.
5. The check valves on the inlet of the thermostatic mixing valve are clean.
PROBLEM 3: INSUFFICIENT or NO WATER FLOW WITHOUT CLICKING SOUND
Check if the shipping covers on the lens are still installed. If so remove the gold opaque lens cover from the bottom of the
sensor lens.
If this doesn't help:
2. Check Battery
Follow steps 1,2 & 3 from the
battery pack replacement
(Problem 1 - page 1)
If this doesn't help : check the sensors
Sanifount
®
- Sensor Operated
INTERSAN
®
SANIFOUNT
®
REPAIR GUIDE