COMMUNICATION PORT DESCRIPTION
OPERATION
The communication port of the controller is compatible with RS485-USB communication for real time monitoring by the PC software of through a
WIFI module (optional) so it can be monitored though the app. The communication port is a standard 8 pin RJ45 interface and the pins are defined
below:
REMARKS
The pin definition only applies to our Cedro controllers
When the load output turns off due to the triggering protection mechanism, the dry contact output interface will turn on (low
impedance).
The controller has dual RS485 communication ports and that can be used for communication and parallel connection.
If it is required to centrally monitor multiple controllers, please set the controllers address (1-254) accordingly. For example: 5
controllers in a parallel connection and with central monitoring will have the controllers’ address order as 1,2,3,4 and 5.
If it is required to centrally monitor multiple controllers as a Master-Slave communication, please set the Master controller address
to 255. For example: 5 controllers in a parallel connection and with central monitoring will just need to set the Master controller’s
address as 255
.
1. PV information
2. Battery information
3. DC load information
4. Load status
5. Working mode
6. System information
PIN Función
1 RS485-A
2 RS485-B
3 Dry contact
4 Dry contact
5 GND
6 GND
7 +5V (Non-Isolated)
8 5V (Non-Isolated)
LCD SCREEN DESCRIPTION
CEDRO CONTROLLER ICC-6048150 / ICC-5048150 / ICC-4048150 / ICC-3048150 / ICC-2048150 / ICC-
4024150 USER MANUAL