[Emergency Stop Devices]
For safety reasons, install the emergency stop devices at station adjacent to solar
inverter combiner in the end system.
The emergency stop of the unit can be enabled using the service switch as required
in section [Isolation device] if this isolation device is installed adjacent to solar
inverter.
[PE Connection and Leakage Current]
The endues application shall monitoring of the protective conductor by a residual
current operated protective device (RCD) with rated fault current Ifn ≤30mA which
automatically disconnects the device in the case of a fault.
WARNINGS
EARTH CONNECTION ESSENTIAL BEFORE CONNECTING SUPPLY
Incorrect grounding can cause physical injury, death or equipment
malfunction and increase electromagnetic interference.
Make sure that grounding conductors are adequately sized as
required by safety regulations.
Do not connect the ground terminals of the unit in series in case of a
multiple installation.
WARNINGS
This product can cause current with an A.C. component. Where a
residual current operated protective (RCD) or monitoring (RCM)
device is used for protection in case of direct or indirect contact, only
an RCD or RCM of Type B is allowed on the supply side of this
product.
[Safety Check]
The following safety checks should be performed at least every 12 months by
manufacturer’s qualified person who has adequate training, knowledge, and
practical experience to perform these tests. The data should be recorded in an
equipment log. If the device is not functioning properly or fails any of tests, the
device has to be repaired.