BPD series PV pumping inverter    Function parameters 
40 
detection of 
underload 
operation 
0.1–100.0% 
If it is 0.0%, it is determined by the inverter. 
If it is not 0.0%, it is determined by P15.17. 100.0% 
corresponds to the rated motor current.   
If the target frequency and the absolute value of the 
ramp  frequency  is  less  than  or  equal  to  P15.19, 
and  the  current  corresponding  to  the  current 
frequency is less than P15.17, after the time set by 
P15.16, it  will report  underload fault; otherwise, it 
will operate normally. If the state is not continuous, 
the delay counting will be cleared automatically. 
0.0–1000.0s 
Underload reset delay 
The operation time and reset time are counted at 
the  same  time  during  underload,  and  it  is  bigger 
than  P15.16  generally  to  ensure  underload 
pre-warning will be reported. After the time set by 
P15.18-P15.16, it will reset. If the value is the same 
as  P15.16,  it  will  reset  when  report  underload 
pre-warning. 
0.00–200.00Hz 
P15.19  is  the  lag  frequency  for  the  analysis  of 
underload operation. If the target frequency and the 
absolute value of the ramp frequency is less than 
or equal to P15.19, the current will be compared.   
0.0–3600.0s 
Delay time of weak light 
If the output frequency is less than or equal to the 
lower  limit  of  PI  output  frequency  and  the  state 
lasts  for  the  set  value,  it  will  report  A-LS  and