Goodrive300 Series VFD    Function parameters 
41 
the password freely and the VFD will work as the last setting one. When P07.00 is set to 0, the 
password can be canceled. If P07.00 is not 0 during powering on, then the parameter is protected by 
the password. When modify the parameters by serial communication, the function of the password 
follows the above rules, too.   
Detailed instruction of parameters 
P00 Group    Basic function group 
0: Sensorless vector control mode 0 (apply to AM 
and SM) 
No need to install encoders. It is suitable in cases 
with  low  frequency,  big  torque  and  high  speed 
control  accuracy  for  accurate  speed  and  torque 
control. Compared to mode 1, this mode is more 
suitable for medium and small power.   
1: Sensorless vector control mode 1 (applying to 
AM) 
No need to install encoders. It is suitable in cases 
with  high  speed  control  accuracy  for  accurate 
speed and torque control at all power ratings.   
2: SVPWM control   
No  need  to  install  encoders.  It  can  improve the 
control  accuracy  with  the  advantages  of  stable 
operation,  valid  low-frequency  torque  boost  and 
current vibration suppression and the functions of 
slip compensation and voltage adjustment.   
Note: AM: Asynchronous motor,   
SM: Synchronous motor; 
Motor  parameter  autotuning  must  be  performed 
on the VFD first when the vector mode is used. 
Select the run command channel of the VFD. 
The  control  command  of  the  VFD  includes: 
start-up, stop, forward, reverse, jogging and fault 
reset. 
0: Keypad ("LOCAL/REMOT" light off) 
Carry  out  the  command  control  by  RUN, 
STOP/RST on the keypad.   
Set  the  multi-function  key  QUICK/JOG  to 
FWD/REVC  shifting  function  (P07.02=3)  to 
change  the  running  direction;  press  RUN  and