*Lorsqu’un LTG est utilisé, il faut lire pour la ‘’borne 10V’’, ‘’borne 18V’’
xxMX – VG 31 or the DNG 31 wiringReturn the wiring to it’s original state. Do the controls work well?MX
xxMX controlsRemove the wire on the ‘EN’ clamp. Does the impeller stop?MX
xxMX controls
Connect up the ‘10V’ and the ‘E
soll
’ clamp. disconnect the ‘E
soll
’ wire.
Does the MX start working in high speed?
MX
xxMX controlsRemove the wire on the ‘E
soll
’ clamp. Does the MX start working in low speed?MX
xVG 31
10V = on the ‘EN UIT’ and the ‘GND’ clamp. The SAG is not at position ‘0’.
0V = on the ‘EN UIT’ and the ‘GND’ clamp. The SAG is at position ‘0’.
VG 31
xVG 31 check the F2 fuseTurn the SAG knob. Does the voltage vary between the ‘E
soll
’ UIT’ clamp and the ‘GND’?VG 31
xxSAG
Knob in position ‘0’, no connection between the ‘10V’* and the ‘EN’ clamp. Knob in any other position,
with connection between ‘10V’ and the ‘EN’ clamp. Is that correct?
SAG
xxSAGTurn the regulator knob. Does the voltage vary on the ‘E
soll
’ and the ‘GND’ clamp?SAG
xx-Return the wiring to it’s original state.SAG
xxMX – SAG cabling
Also connect up the ‘10V’* and the ‘E
soll
’ clamp.
Disconnect the ‘E
soll
’ wire. Does the MX start working in high speed?
SAG
xxMX – SAG cablingConnect up the ‘10V’* and the ‘EN’ clamp. Does the MX start working in low speed?SAG
xx
MX – SAG cabling
Is there release applied?
Set the SAG to the ‘0’ position. Does the MX switch off?
SAG
xxMX – SAG cablingIs there 10V = on the ‘10V’* and the ‘GND’ clamp?SAG
xReturn the wiring to it’s original state.MX
xMX controlsRemove the wire on the ‘EN’ clamp. Does the impeller stop?MX
xMX controls
Connect up ‘10V’ and the ‘E
soll
’ clamp. Disconnect the ‘E
soll
’ wire.
Does the MX start working in high speed?
MX
xMX controls
Remove the wire on the ‘E
soll
’ clamp. does the MX start working in low speed?
MX
xDNG 31 check the F2 fuseSwitch the timer manually. Does the voltage vary between the ‘E
soll
UIT’ and the ‘GND’?DNG 31
x
DNG 31 timer. See also the timer manual
for the timer control.
Switch the timer manually. Does the voltage vary between the ‘E
soll
IN’ and the ‘GND’?DNG 31
xDNG 31
Adjust potentio-meter R2. Does the voltage vary between clamp ‘2’ and the ‘GND’?
(Reset the potentio-meter to the same voltage).
DNG 31
xDNG 31
Adjust potentio-meter R1. Does the voltage vary between clamp ‘1’ and the ‘GND’?
(Reset the potentio-meter to the same voltage).
DNG 31
xDNG 31
10V = on the clamps ‘EN UIT’ and the ‘GND’ swicht on
0V = on the clamps ‘EN UIT’ and the ‘GND’ swicht on
DNG 31
xxVG 31 or DNG 31, Check the F3 fuse.10V = on the ‘+10V’ and the ‘GND’?
VG 31 or
DNG 31
xxelectrical installation230V~ on the ‘L’and thet ‘N’ clamp?
VG 31 or
DNG 31
DNG 31
SAG or
LTG +
VG31
SAG 0-2,
SAG 0-5,
SAG 0-M, LTG
If no, then the malfuntion is in the:Check to be carried out, if yes then go to next line:Carry out