2. DO NOT connect the 45710 auxiliary switch to the
home’s black Hot (Line) wire.
Observe Important Wiring Information
Important: This switch is rated for and intended to
only be used with copper wire.
The home’s electrical wires may be attached to the screw
terminals or inserted into the holes in the back of the
switch enclosure and clamped in place by tightening
the screw terminals. Always follow the recommended
wire strip lengths when making wiring connections.
Wire strip length:
• For attachment to screw terminals: Strip insulation 1
25mm (14 AWG wire).
• For attachment using the enclosure’s holes: Strip
insulation 5/8” 16mm (14 AWG wire).
Wire gauge requirements
Use 14 AWG or larger wires suitable for at least 176°F
80°C for supply (HOT), Load, Neutral and Traveler
connections.
Use 14 AWG or larger wires suitable for 176°F 80°C for