JET Digital Pressurisation Equipment
MAXI Models (D125, D225, D150, D250)
MD Models (125, 225, 150, 250)
Mini Models (130D, 230D)
Operation & Maintenance
Manual
Rev 8.1

Questions and Answers

  • J
    Jennifer ParkSep 3, 2025
    What does HIGH H20 fault mean on my Jet MAXI D125 Heating System?
    • D
      Daniel ThomasSep 3, 2025
      If the HIGH H20 fault is displayed on your Jet Heating System, it could be caused by: * A non-standard electrical connection has been made into terminals 21 & 22. Remove all non-standard electrical connections. * The digital controller has failed. Replace digital controller.
  • R
    robertscottSep 18, 2025
    What does SERVICE displayed on the screen mean for my Jet MAXI D125 Heating System?
    • S
      Stephen PerrySep 18, 2025
      If SERVICE is displayed on the screen of your Jet Heating System, the unit is due an annual service. Contact service engineer.
  • A
    akennedySep 16, 2025
    Why don't the buttons on the digital controller respond on my Jet MAXI D125?
    • K
      Kelly MorenoSep 16, 2025
      If the buttons on the digital controller of your Jet Heating System aren't responding, the plastic housing of the digital controller may have come apart and the PCB has moved. Reassemble the digital controller housing and ensure that the PCB is properly seated.
  • J
    John KellySep 14, 2025
    Why are the digital controller parameters being corrupted on my Jet MAXI D125?
    • M
      morenorandySep 14, 2025
      If the digital controller parameters on your Jet Heating System are being corrupted, the controller might be subject to power spikes. Fit a suitable power filter to resolve this.
  • B
    Bailey BishopSep 12, 2025
    What to do if P2 FAIL is displayed on a single pump Jet MAXI D125?
    • C
      Catherine FlowersSep 12, 2025
      If P2 FAIL is displayed on your Jet Heating System, but it's a single pump model, the PUMPS NUMBER option is likely incorrectly set to 2. Change the PUMPS NUMBER setting to 1.
  • J
    James MurphySep 12, 2025
    Why does the pump persistently become air-locked in my Jet MAXI D125 Heating System?
    • J
      John CarrilloSep 12, 2025
      If the pump in your Jet Heating System keeps becoming air-locked, it could be because the wrong or no flow restrictor is installed in the float valve (mini and midi units only). Check float valve flow restrictor selection (mini and midi units only).
  • R
    ryanhudsonSep 9, 2025
    What should I do if the pump runs but doesn't make up pressure in my Jet MAXI D125?
    • T
      turnerrussellSep 9, 2025
      If the pump runs but doesn't build pressure in your Jet Heating System, it's likely that the pump is air-locked and not pumping water. Bleed the pump to resolve this.
  • R
    robin82Sep 7, 2025
    Why doesn't the digital controller power up on my Jet MAXI D125?
    • K
      kedwardsSep 7, 2025
      If the digital controller on your Jet Heating System isn't powering up when you switch on the unit, check these: * The fuse has blown. Replace the fuse. * The mains power supply is at an incorrect voltage or frequency. Check mains power supply. * The 12V transformer has failed. Replace Transformer. * The digital controller has failed. Replace digital controller.
  • K
    Kimberly LopezSep 5, 2025
    What does P1 and/or P2 FAIL mean on my Jet MAXI D125?
    • D
      Douglas ClaytonSep 5, 2025
      If P1 and/or P2 FAIL is displayed on your Jet Heating System, it might be because: * The PUMP TYPE option is set incorrectly. Review PUMP TYPE setting. * The relevant pump has failed. Replace pump.
  • A
    Alexander MunozAug 20, 2025
    What to do if the LOW PRESSURE fault is displayed and the pumps do not run on my Jet Heating System?
    • J
      Jeffrey PriceAug 20, 2025
      If the LOW PRESSURE fault is showing and the pumps aren't running on your Jet Heating System, here's what might be happening: * The internal isolation valve within the unit could be closed. If so, open the internal isolation valve. * The system pressure might have dropped below the LOW PRESSURE set point. To fix this, increase system pressure using a filling loop, or enable the SYSTEM FILL option. * The SPC CONTROLLER option might be enabled. Try disabling the SPC CONTROLLER option. * The LOW PRESSURE set point might be too high. In this case, review the system specifications.

Summary

Installation

Electrical Power Supply

Details electrical connection requirements, safety, and isolation for the unit.

Micro Controller

Commissioning

Pre-Commissioning Checklist

Lists essential conditions to verify before starting the commissioning process.

Controller Programming

Explains how to access and modify controller settings using access codes.

Program List

Details all menu items, their functions, and default values for configuration.

Hydraulic Commissioning

Initial Start-up

Testing

Procedure to test the unit's operation by simulating a minor pressure leak.

Operation

Fault Codes

Lists and explains all fault codes displayed by the digital controller.

Maintenance

Wiring Diagram

Troubleshooting

LOW PRESSURE Fault

Addresses issues when the LOW PRESSURE fault is displayed and pumps do not run.

HIGH PRESSURE Fault

Addresses issues when the HIGH PRESSURE fault is displayed.

P1;P2 FLOOD LIMIT Fault

Addresses issues when P1 or P2 FLOOD LIMIT faults are displayed.

P1;P2 FAIL Faults

Addresses issues when P1 or P2 FAIL faults are displayed.

LOW;HIGH H20 Faults

Addresses issues related to low or high water level faults.

Pressure Mismatch & ERROR 1

Addresses issues with pressure readings and sensor errors.

Pump Performance Issues

Addresses pumps not making pressure or becoming air-locked.