What to do if the LOW PRESSURE fault is displayed and the pumps do not run on my Jet Heating System?
- JJeffrey PriceAug 20, 2025
If the LOW PRESSURE fault is showing and the pumps aren't running on your Jet Heating System, here's what might be happening: * The internal isolation valve within the unit could be closed. If so, open the internal isolation valve. * The system pressure might have dropped below the LOW PRESSURE set point. To fix this, increase system pressure using a filling loop, or enable the SYSTEM FILL option. * The SPC CONTROLLER option might be enabled. Try disabling the SPC CONTROLLER option. * The LOW PRESSURE set point might be too high. In this case, review the system specifications.