Questions and Answers

  • J
    jacksonchristopherSep 2, 2025
    What does ERROR 1 fault mean on my Jet MAXI D125 Heating System?
    • R
      Ryan MaysSep 2, 2025
      If ERROR 1 fault is displayed on your Jet Heating System, this could be due to: * The SENSOR TYPE option is set incorrectly. Review SENSOR TYPE setting. * The pressure sensor has failed. Replace pressure sensor.
  • A
    Amy GoldenAug 31, 2025
    What does P1 and/or P2 FLOOD LIMIT mean on my Jet MAXI D125?
    • A
      ajonesAug 31, 2025
      If P1 and/or P2 FLOOD LIMIT is displayed on your Jet Heating System, it could be due to these reasons: * A large amount of water has been lost from the system. Investigate cause. * The relevant pump is air-locked and not pumping water. Bleed the pump. * The unit is undersized for the system. Review unit selection. * The FLOOD LIMIT time is too short. Consult Wolseley.
  • R
    ramosjacquelineAug 29, 2025
    What does it mean when the LOW H20 fault is displayed on a Jet MAXI D125?
    • J
      Jennifer MooreAug 29, 2025
      If the LOW H20 fault is displayed on your Jet Heating System, it could be due to: * The mains water supply to the unit has been isolated. Turn on the mains water supply. * The mains pressure is poor. The fault will clear once the break tank has been re-filled. * A non-standard electrical connection has been made into terminals 19 & 20. Remove all non-standard electrical connections. * The low water float switch has failed. Replace low water float switch. * The digital controller has failed. Replace digital controller.
  • C
    Charles Ruiz MDAug 28, 2025
    Why does the pump repeatedly run in short bursts in my Jet Heating System?
    • B
      Bradley FinleyAug 28, 2025
      If the pump in your Jet Heating System is repeatedly running in short bursts, here are a few possible reasons: * The internal isolation valve within the unit is partially closed. Fully open the internal isolation valve. * The restriction in the connecting pipe work is too great. Increase bore, reduce number of bends, or reduce length of connecting pipe work. * A pump non-return valve has failed. Replace non-return valve. * The expansion vessel has failed or lost its pre-charge. Check the expansion vessel pre-charge and re-charge if necessary. * The point of connection of the unit is too far away from the expansion vessel. Move unit/expansion vessel connection points closer together.
  • R
    rluceroAug 26, 2025
    Why doesn't the pressure reading match the actual system pressure on my Jet MAXI D125 Heating System?
    • K
      Kristy DeleonAug 26, 2025
      If the pressure reading on your Jet Heating System doesn't match the actual system pressure, consider these potential causes: * The internal isolation valve within the unit is closed. Open the internal isolation valve. * The SENSOR TYPE option is set incorrectly. Review the SENSOR TYPE setting. * A non-return valve has been installed between the unit and the system. Remove the non-return valve. * The pressure sensor has failed. Replace the pressure sensor.
  • K
    Kelsey BellAug 25, 2025
    What causes the break tank to overfill in my Jet MAXI D125?
    • L
      lschroederAug 25, 2025
      If the break tank in your Jet Heating System is overfilling, consider the following possible causes: * The wrong or no flow restrictor is installed in the float valve (mini and midi units only). Check the float valve flow restrictor selection (mini and midi units only). * The float valve position is set incorrectly. Set the float valve to its lowest possible position. * The float valve has failed. Replace the float valve. * A pump non-return valve has failed. Replace the non-return valve.
  • C
    Clayton HarrisonAug 22, 2025
    Why is the HIGH PRESSURE fault displayed on my Jet MAXI D125?
    • J
      Joyce LoganAug 22, 2025
      If a HIGH PRESSURE fault is displayed on your Jet Heating System, it could be due to several reasons: * The internal isolation valve within the unit is closed, so you should open it. * The system pressure has risen above the HIGH PRESSURE set point, so you should decrease system pressure using a suitable drain point. * The expansion vessel has failed or lost its pre-charge, so check the expansion vessel pre-charge and re-charge if necessary. * The expansion vessel is undersized, so review the expansion vessel selection. * The HIGH PRESSURE set point is too low, so review the system specifications.

Summary

Installation

Electrical Power Supply

Details electrical connection requirements, safety, and isolation for the unit.

Micro Controller

Commissioning

Pre-Commissioning Checklist

Lists essential conditions to verify before starting the commissioning process.

Controller Programming

Explains how to access and modify controller settings using access codes.

Program List

Details all menu items, their functions, and default values for configuration.

Hydraulic Commissioning

Initial Start-up

Testing

Procedure to test the unit's operation by simulating a minor pressure leak.

Operation

Fault Codes

Lists and explains all fault codes displayed by the digital controller.

Maintenance

Wiring Diagram

Troubleshooting

LOW PRESSURE Fault

Addresses issues when the LOW PRESSURE fault is displayed and pumps do not run.

HIGH PRESSURE Fault

Addresses issues when the HIGH PRESSURE fault is displayed.

P1;P2 FLOOD LIMIT Fault

Addresses issues when P1 or P2 FLOOD LIMIT faults are displayed.

P1;P2 FAIL Faults

Addresses issues when P1 or P2 FAIL faults are displayed.

LOW;HIGH H20 Faults

Addresses issues related to low or high water level faults.

Pressure Mismatch & ERROR 1

Addresses issues with pressure readings and sensor errors.

Pump Performance Issues