Operating manual
TELIS 9000
Version of 03/30/2023
Question and Answer IconNeed help?

Do you have a question about the JM Concept TELIS 9000 and is the answer not in the manual?

Overview

The TELIS 9000 is a universal input transmitter designed for precise measurement and control in industrial applications. It features quadruple galvanic isolation, 24-bit conversion for inputs, and 16-bit conversion for outputs, ensuring high accuracy and reliability. The device is guaranteed for 5 years, highlighting its robust construction and quality.

Function Description

The TELIS 9000 serves as a universal input transmitter capable of handling various sensor types and providing corresponding outputs. It supports both single and dual current passive mA inputs with a calculation mode, allowing for complex signal processing. The device offers extensive programming capabilities, accessible via a front-panel joystick or a PC using the IXLOG software.

Key functions include:

  • Input Processing: Converts signals from a wide range of sensors into standardized outputs.
  • Output Generation: Produces analog current (0-10mA, 0-20mA, 4-20mA) and voltage (0-10V, ±10V, 0-5V, 1-5V, 2-10V) outputs, as well as relay outputs (1RT or 1T).
  • Communication: Features isolated USB on the front panel and isolated RS485 Modbus RTU for digital communication, configuration, and control.
  • Display and Monitoring: Equipped with a backlit LCD screen (5 characters, 5 lines, blue color) for visualizing inputs, outputs, and alarm statuses. Devices without a display have a green LED indicator.
  • Alarm Management: Supports up to four alarms with configurable thresholds, hysteresis, time delays, and relay assignments. Alarms can be acknowledged and their statuses stored.
  • Simulation Function: Allows users to simulate input values to test analog output values and relay statuses without actual sensor input.
  • Calculation Mode: For dual current inputs, it can perform calculations (+, -, x, /) on the input signals, with the result available on input 3.
  • Segmentation: Offers linearization in up to 99 points for creating custom output functions based on input signal segmentation. It also supports PTC/NTC curve creation via IXLOG software.
  • Filtering: Integrates measurements over a defined time to smooth out signal variations.
  • Offset and Tare: Provides manual adjustment of input offset and a taring function for current, voltage, and potentiometer inputs.
  • Cut-off: Defines a threshold below which the input is considered null, preventing display of very low or noisy signals.
  • Absolute Value and Square Root: Can configure outputs to be a function of the absolute value of a bidirectional input or the square root of the input.

Important Technical Specifications

  • Input Types:
    • Current (continuous): Standard scales (0-1mA, 0-10mA, 0-20mA, 4-20mA, ±1mA, ±10mA, ±20mA); adjustable from -22 to 22mA. Input impedance: 5.6Ω.
    • Voltage (continuous): Standard scales (0-100mV, 0-1V, 0-5V, 1-5V, 0-10V, 2-10V, ±100mV, ±1V, ±5V, ±10V, 0-50V, 0-100V, 0-200V, 0-500V, 0-1000V, ±50V, ±100V, ±200V, ±500V, ±1000V); adjustable from -110 to 110mV, from -2 to 11V, from -1000 to 1000V. Input impedance: >10MΩ (U<10V), 6MΩ (U±10V or >10V).
    • Variable Resistance Thermometer (RTD): PT10, PT100, PT1000, Ni100, Ni1000 (2 or 3 wires); adjustable scales (CU50, CU53, CU100). Current input: <1mA (PT100, Ni100), <0.8mA (PT1000, Ni1000).
    • Resistance (2 wires): Standard scales (200Ω, 1KΩ, 10KΩ, 50KΩ); adjustable scales (200Ω, 1KΩ, 10KΩ, 50KΩ programmable with IXLOG software). Current input: <1mA (R=200Ω, R=1kΩ), <0.2mA (R=10KΩ).
    • Thermocouple: Standard scales (J, K, R, S, T, E, B, N, W3/D, W5/C, Mo, P); adjustable scales (J, K, R, S, T, E, B, N, W3/D, W5/C, Mo, P). Cold junction compensation: internal or external.
    • Potentiometer: From 0-100Ω to 0-100KΩ.
    • Sensor Supply: 2 or 3 wires sensor 24V - 32mA max (only in 1 channel input mode).
  • Output Types:
    • Current (1 & 2): Standard scales (0-10mA, 0-20mA, 4-20mA); adjustable from 0 to 20mA. Permissible impedance: <1KΩ.
    • Voltage (1 & 2): Standard scales (0-10V, ±10V, 0-5V, 1-5V, 2-10V); adjustable from -10 to 10V (Output 1), from 0 to 10V (Output 2). Permissible impedance: >1KΩ.
    • Relay: 1RT or 1T, 2A-250Vac.
  • General Characteristics:
    • Precision Class: 0.1
    • Input A/D Conversion: 24 bits
    • Output A/D Conversion: 16 bits
    • Response Time: <80ms (process input, thermocouple, 2 wires resistor), <160ms (RTD potentiometer).
    • Thermal Drift: <25ppm
    • Residual Ripple: <20μA (current output), <10mV (voltage output).
    • Maximum Consumption: <10VA
    • Operating Temperature: -10°C to +60°C
    • Storage Temperature: -25°C to +80°C
    • Protection Factor: IP20 (Black self-extinguishing polyamide housing V0).
  • Isolation:
    • Supply/Input-Output(s)-Relay-RS485-USB: 4200Vrms, 50Hz, 1mn
    • Input/Output 1/Output 2/Relay/RS485: 2500Vrms, 50Hz, 1mn
    • USB/Input: 2500Vrms, 50Hz, 1mn
    • USB/Output 1-relay: 2500Vrms, 50Hz, 1mn
    • USB/RS485: 2500Vrms, 50Hz, 1mn
  • Auxiliary Source: 22-240Vdc or 90-230Vac 50/60Hz.

Usage Features

  • Universal Input: The TELIS 9000 is highly versatile, accepting signals from a wide array of sensors, making it suitable for diverse industrial applications.
  • Hot-Swappable Design: The module can be plugged in and out of its baseline while powered, facilitating maintenance and system upgrades without interrupting operations.
  • User-Friendly Interface: Programming can be done directly on the front panel using a 5-position joystick and LCD display, or via PC software (IXLOG) for more advanced configurations.
  • Graphical Display: The LCD screen provides clear visualization of input values, programmed values, and alarm statuses, enhancing operational awareness.
  • Memory Mini/Maxi: Stores the maximum and minimum measured values for each input channel, useful for monitoring process extremes.
  • Customizable Display: Allows adjustment of resolution, decimal point, and contrast, and offers a "display off" option for power saving or specific operational needs.
  • Modbus RTU Communication: Enables seamless integration into existing Modbus networks for remote monitoring, configuration, and control. The device acts as a slave, responding to queries from a master device (e.g., PLC).
  • PC Programming (IXLOG Software): The IXLOG software provides an advanced, user-friendly human/machine interface for programming, backup, copy/paste configurations, device detection, and real-time measurement visualization.
  • Safety Features: Includes programming lock to prevent unauthorized changes and sensor signal loss detection, which translates to display messages, analog output adjustments, digital output changes, and relay status updates.

Maintenance Features

  • Easy Cleaning: The device can be cleaned by switching it off and using a cloth slightly moistened with distilled water.
  • Modular Design: The hot-swappable module simplifies replacement and repair.
  • Factory Repair: All repairs are exclusively carried out at JM Concept's premises to ensure quality and maintain the warranty.
  • Protective Fuse Recommendation: An external time-delayed fuse (T 500mA 250V) with a high cut-off power is recommended to protect the external power supply, as the product itself is not equipped with one.
  • Storage Conditions: Must be stored in its packaging in a room protected from dust, moisture, and mechanical vibration, within a temperature range of -25°C to +80°C.
  • Installation Guidelines: Detailed instructions for mounting on a DIN rail and wiring are provided, including recommendations for wire section, stripping length, and tightening torque, to ensure proper and safe installation.
  • Environmental Considerations: Designed for indoor use in an electrical box, within specified ambient temperatures (-10°C to +60°C), and capable of withstanding grid fluctuations of +/-10% on its voltage supply.
  • Insulation Level: External circuits connected to inputs and outputs should have an insulation level of 2500Vrms to maintain the device's internal insulation.

JM Concept TELIS 9000 Specifications

General IconGeneral
BrandJM Concept
ModelTELIS 9000
CategoryTransmitter
LanguageEnglish