ANSUL Cartridge Dry Chemical Fire Extinguishers
Models 10, 20, 30, Operation, Inspection, Service and
Maintenance, and Recharge Manual (Form No. F-7674)
INTRODUCTION
PAGE 2 REV. 10 2018-OCT-15
RECORD KEEPING (Continued)
A separate label shall also be affixed to the extinguisher
following a successful hydrostatic test. This label shall include
the month and year the test was performed, the test pressure
used, and the name or initials of the person performing the
test. This label shall be self-destructive when removal from the
extinguisher is attempted.
In addition to the required tags or labels, a permanent file
record should be kept for each extinguisher. This file record
should include the maintenance date and the name of the
person performing the maintenance, the date when last
recharged and the name of the person or agency performing
the hydrostatic test, and a description of the extinguisher’s
physical condition after passing a hydrostatic test.
Parts of above were taken from the latest edition of NFPA 10,
Standard for Portable Fire Extinguishers.
PARTS LISTS
To order parts lists, contact Johnson Controls Customer
Services, Marinette, WI 54143-2542.
REFERENCES
REFERENCES IN THIS MANUAL: AVAILABLE FROM:
NFPA-10 “STANDARD FOR NFPA
PORTABLE FIRE 1 Batterymarch Park
EXTINGUISHERS” Quincy, MA 02169-7471
CGA C-1 “METHODS FOR Compressed Gas
HYDROSTATIC Association
TESTING OF 14501 George
COMPRESSED Carter Way, Suite 103
GAS CYLINDERS” Chantilly, VA 20151-1788
CGA C-6 “STANDARD FOR
VISUAL INSPECTION
OF STEEL
COMPRESSED
GAS CYLINDERS”