ANSUL Cartridge Dry Chemical Fire Extinguishers
Models 10, 20, 30, Operation, Inspection, Service and
Maintenance, and Recharge Manual (Form No. F-7674)
PAGE 16 REV. 10 2018-OCT-15
MAINTENANCE
MAINTENANCE (Continued)
39. After cleaning the extinguisher to remove all dry chemi-
cal traces and foreign deposits, insert and secure visual
seal, Part No. 15999, through puncture lever (over hose)
and hose confiner attachment on the shell. Note: If extin-
guisher has a composite cartridge guard, insert visual
seal through puncture lever and then through hole in
guard. If provided, attach tamper-proof seal (Part No.
15999) through puncture lever, through hole in fill cap,
and back around to connect this seal. On ring pin models,
a second visual seal is required for insertion through the
first link of the chain on the guard and around through the
ring of the pin.
40. Return the extinguisher to its designated location.
41. Personnel making maintenance checks are usually
required to keep records by way of marking a tag
attached or affixed to the extinguisher and/or in a
permanent file. Your precise guide to record keeping
requirements should be the applicable company, local,
state or federal authority having jurisdiction.
40 003189 39 003190
41 003200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls ANSUL 10 and is the answer not in the manual?

Johnson Controls ANSUL 10 Specifications

General IconGeneral
BrandJohnson Controls
ModelANSUL 10
CategoryFire Extinguisher
LanguageEnglish