Installation Manual for Multi-Kits
Line Branch Models: MW-NP282A3, MW-NP452A3, MW-NP692A3, MW-NP902A3
After installation, it is recommended to give this manual to customer for future reference.
NOTICE
1. Applicable Outdoor Units
These multiple line branches can be applied to the R410A VRF systems.
2. Transportation
Transport this product as close to the installation site as practical before unpacking. Do not discard any foam
packaging as it is used as insulation for the joint kits after pressure testing is complete.
Do not place any material on this product.
Important Notice
Ɣ Johnson Controls-Hitachi Air Conditioning pursues a policy of continuing improvement in design and
performance of its products. As such, Johnson Controls-Hitachi Air Conditioning reserves the right to make
changes at any time without prior notice.
Ɣ Johnson Controls-Hitachi Air Conditioning cannot anticipate every possible circumstance that might involve a
potential hazard.
Ɣ This heat pump air conditioning unit is designed for standard air conditioning applications only. Do not use
this unit for anything other than the purposes for which it was intended for.
Ɣ 7KHLQVWDOOHUDQGV\VWHPVSHFLDOLVWVKDOOVDIHJXDUGDJDLQVWOHDNDJHLQDFFRUGDQFHZLWKORFDOSLSH¿WWHUDQG
electrical codes. The following standards may be applicable, if local regulations are not available. International
Organization for Standardization: (ISO 5149 or European Standard, EN 378). No part of this manual may be
reproduced in any way without the expressed written consent of Johnson Controls-Hitachi Air Conditioning.
Ɣ This heat pump air conditioning unit will be operated and serviced in the United States of America and comes
with a full complement of the appropriate Safety, Danger, and Caution, warnings.
Ɣ If you have questions, please contact your distributor or dealer.
Ɣ This manual provides common descriptions, basic and advanced information to maintain and service this heat
pump air conditioning unit which you operate as well for other models.
Ɣ This manual should be considered as a permanent part of the air conditioning equipment and should remain
with the air conditioning equipment.
Product Inspection upon Arrival
1. Upon receiving this product, inspect it for any damages incurred in transit. Claims for damage, either apparent
RUFRQFHDOHGVKRXOGEH¿OHGLPPHGLDWHO\ZLWKWKHVKLSSLQJFRPSDQ\
2. Check the model number, electrical characteristics (power supply, voltage, and frequency rating), and any
accessories to determine if they agree with the purchase order.
3. The standard utilization for this unit is explained in these instructions. Use of this equipment for purposes
other than what it designed for is not recommended.
4. Please contact your local agent or contractor as any issues involving installation, performance, or
PDLQWHQDQFHDULVH/LDELOLW\GRHVQRWFRYHUGHIHFWVRULJLQDWLQJIURPXQDXWKRUL]HGPRGL¿FDWLRQVSHUIRUPHG
by a customer without the written consent of Johnson Controls-Hitachi Air Conditioning. Performing any
mechanical alterations on this product without the consent of the manufacturer will render your warranty null
and void.
Question and Answer IconNeed help?

Do you have a question about the Johnson Controls Hitachi MW-NP282A3 and is the answer not in the manual?

Johnson Controls Hitachi MW-NP282A3 Specifications

General IconGeneral
BrandJohnson Controls
ModelHitachi MW-NP282A3
CategoryAir Conditioner
LanguageEnglish

Summary

General Precautions

Safety Devices and Interlocks

Do not adjust or bypass safety devices; ensure they are in place and functioning correctly for safe operation.

Unauthorized Modifications

Unauthorized modifications void warranty, create hazards, and may violate regulations or standards.

Installation Precautions

Prohibited Installation Locations

Avoid locations with explosive atmosphere, fire hazards, corrosive gases, high acidity, or decomposition gases.

Brazing Safety Precautions

Ensure no flammable materials or open flames are present before brazing; use safety guards during operation.

Refrigerant Precautions

Refrigerant Type and Compliance

Use only approved refrigerants. Non-approved substitutes void warranty and increase injury risk.

Refrigerant Concentration in Small Rooms

In small rooms, take measures to prevent refrigerant exceeding maximum allowable concentration per ASHRAE standards.

Refrigerant Leak Testing

Perform refrigerant leak tests before installation completion. Ventilate if leaks occur and contact service.

Piping Connection and Compressor Start

Connect piping securely before starting the compressor. Avoid high pressure from premature compressor activation.

Flare Nut Tightening

Tighten flare nuts with a torque wrench to specified values. Do not overtighten to prevent cracking and leakage.

Pressurized System Safety

Never loosen threaded joints or open pressurized parts. Dismantle piping only after compressor stops.

Electrical Precautions

Wiring Diagram and Grounding

Refer to wiring diagrams and instructions. Improper connections or grounding can cause serious injury or death.

Service Disconnects

Open and tag all disconnect switches before servicing. Verify power is off using a meter.

Power Supply and Circuit Breakers

Use an exclusive power supply at rated voltage. Install circuit breakers with specified capacity and tighten terminals.

Installation Work

Piping from Multi-Kit to Indoor Unit

Connection Procedure for Piping Joint

Piping Work

Refrigerant Piping Safety

Refrigerant Leak Hazards

Leaking refrigerant can form toxic gases with sparks or cause suffocation as it's heavier than air.