TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
39
Equipment Setup General
Unit Type 4-Pipe 2-Pipe, 4-Pipe, VAV
Heating/Cooling Device Type* Floating On/Off, Floating
* Fan coil units only
Actuator Stroke Time* 30 seconds 5 to 300
* Floating Heating/Cooling device type
only
Cooling Min On Time* 120 seconds 0 to 360 seconds
* Fan coil on/off units only
Cooling Min Off Time* 120 seconds 0 to 360 seconds
* Fan coil on/off units only
Heating Min On Time* 120 seconds 0 to 360 seconds
* Fan coil on/off units only
Heating Min Off Time* 120 seconds 0 to 360 seconds
* Fan coil on/off units only
Unoccupied Off Delay 10 minutes 0 to 10 minutes
Supply Fan
Supply Fan Type* Single-Speed Single-Speed, Multi-Speed,
Variable-Speed
* Fan coil units only
Start Voltage* 2 VDC 0 to 10 VDC
* Fan coil units only, variable-speed fan
Full Speed Voltage* 10 VDC 0 to 10 VDC, proportional
*Fan coil units only, variable-speed fan
Table 10: Menus and Submenus (Part 6 of 9)
Level 1 Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values
1