Johnson Controls VMA1617 User Manual

Johnson Controls VMA1617
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
LED status and states
Table 10: Status LEDs and description of LED states
LED label LED color Normal state Descriptions of LED states
POWER Green On Steady
Off Steady = No power
On Steady = Power is supplied by primary voltage
FAULT Red Off Steady
Blink - 2 Hz = Download or startup in progress, not
ready for normal operation, SA Bus devices offline
(such as netsensors)
Rapid blink = SA Bus communications issue
Off Steady = No faults
On Steady = Device fault or no application loaded
FC BUS Green Blink - 2 Hz
Blink - 2 Hz = Data transmission (normal
communication)
Off Steady = No data transmission (auto baud in
progress)
On Steady = communication lost, waiting to join
communication ring
SA BUS Green Blink - 2 Hz
Blink - 2 Hz = Data transmission (normal
communication)
Off Steady = No data transmission (N/A - auto baud
not supported)
On Steady = Communication lost; waiting to join
communication ring
EOL Amber Off
On Steady = EOL is active
Off Steady = EOL is not active
Accessories
Table 11: VMA1617 and VMA1632 Controller Accessories (Order Separately)
Product code number Description
IOM Series Controllers
Refer to the Metasys
®
System Field Equipment Controllers and Related Products Product Bulletin
(LIT-12011042) for a complete list of available IOM Series Controllers.
Mobile Access Portal (MAP) Gateway
Refer to the Mobile Access Portal Gateway Catalog Page (LIT-1900869) to identify the
appropriate product for your region.
MS-DIS1710-0
Local Controller Display
MS-BTCVTCBL-700
Cable Replacement Set for the MS-BTCVT-1 or the NS-ATV7003-0; includes One 1.5 m (5 ft)
Retractable Cable
Y64T15-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 92 VA, Foot Mount, 72.2 cm (30
in.), Primary Leads and 76.2 cm (30 in.) Secondary Leads, Class 2
Y65A13-0
Transformer, 120 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount (Y65AS), 20.32 cm (8
in.), Primary Leads and 76.2 cm (30 in.) Secondary Leads, Class 2
Y65T42-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Hub Mount (Y65SP+),
20.32 cm (8 in.), Primary Leads and Secondary Screw Terminals, Class 2
Y65T31-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount (Y65AR+),
20.32 cm (8 in.), Primary Leads and Secondary Screw Terminals, Class 2
AP-TBK1002-0 2-position Screw Terminal that plugs onto VMA Output Point Spade Lugs
AP-TBK1003-0 3-position Screw Terminal that plugs onto VMA Output Point Spade Lugs
AP-TBK4SA-0 Replacement MS/TP SA Bus Terminal, 4-Position Connector, Brown, Bulk Pack of 10
AP-TBK4FC-0 Replacement MS/TP FC Bus Terminal, 4-Position Connector, Blue, Bulk Pack of 10
AP-TBK2PW-0 Replacement Power Terminal, 2-Position Connector, Gray, Bulk Pack of 10
AS-CBLTSTAT-0 Cable adapter for connection to 8-pin TE-6700 Series sensors
VMA1617 and VMA1632 VAV Controllers Installation Guide20

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls VMA1617 and is the answer not in the manual?

Johnson Controls VMA1617 Specifications

General IconGeneral
BrandJohnson Controls
ModelVMA1617
CategoryController
LanguageEnglish