Using the fieldbus for miscellaneous drive control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied command(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent – the
table shows samples.)
1. Applies only for Modbus using YORK Drive profile.
2. BACnet not defined at time of publication.
3. Use Memorize Point command.
!+&,,2,2
Using the fieldbus for relay output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location. (The location is defined by the Protocol Reference, which is protocol
dependent.)
%@, #,,7
%2,2=2!4=
23;
F \" J,
F
1601 RUN ENABLE 7 (COMM) Run enable by fieldbus. 40001
bit 3
BO4 35
1604
FAULT RESET
SEL
8 (COMM) Fault reset by fieldbus. 40001
bit 7
BO6 94
1607
PARAM SAVE 1 (SAVE) Saves altered parameters
to memory (then value
returns to 0).
41607 BO18 N/A
3
%@, #,,7
%2,2=2!4=
23;
F
F \" J,
Q
1401 RELAY OUTPUT 135 (COMM) Relay Output 1
controlled by
fieldbus.
40134
bit 0 or
00033
BO7 40
1402
RELAY OUTPUT 235 (COMM) Relay Output 2
controlled by
fieldbus.
40134
bit 1 or
00034
BO8 41
1403
RELAY OUTPUT 335 (COMM) Relay Output 3
controlled by
fieldbus.
40134
bit 2 or
00035
BO9 42
1410
1
RELAY OUTPUT 435 (COMM) Relay Output 4
controlled by
fieldbus.
40134
bit 3 or
00036
BO10 43
1411
1
RELAY OUTPUT 535 (COMM) Relay Output 5
controlled by
fieldbus.
40134
bit 4 or
00037
BO11 44
1412
1
RELAY OUTPUT 635 (COMM) Relay Output 6
controlled by
fieldbus.
40134
bit 5 or
00038
BO12 45