Service
Information
How to Drain, Flush, Fill and Vent PYT Model and
HYP Model Drive Coolant Loops
File In/With:
Equipment
Affected:
YZ, YMC2, YK, YD and YKEP Chillers
SI0270
Product Technical Support
GENERAL
This service information letter provides detailed steps required to drain, flush, fill and vent the cooling loop for the
PYT and HYP families of variable speed drives. Please note there are multiple sections in this document that may
appear to be very similar but contain different instructions depending on the model drive. Sections are defined by
drive size and/or model number. All steps are to be followed completely to insure the concentrations are correct and
to prevent the introduction of air into the system.
Items Required
Rubber gloves - purchase locally
5 gallon bucket to contain uids drained from the drive - purchase locally
Inhibitor, see appropriate Table for coolant/inhibitor/distilled water quantities based on drive model
JCI Inhibitor, 5 gallon container (P/N 013 04128 000), see appropriate Table for quantities based on drive
JCI Inhibitor, 1 gallon container (P/N 013 04129 000), see appropriate Table for quantities based on drive
model
De-mineralized water, 1 gallon container (P/N 013 04143 000), or 1 gallon distilled water purchased locally,
see appropriate Table for quantities based on drive model
Work on this equipment should only be done by properly trained personnel who are qualied to work on this
type of equipment. Failure to comply with this requirement could expose the worker, the equipment and the building
and its inhabitants to the risk of injury or property damage.
The instructions on this service information letter are written assuming the individual who will perform this work
is a fully trained HVAC & R journeyman or equivalent, certied in refrigerant handling and recovery techniques, and
knowledgeable with regard to electrical lock out/tag out procedures. The individual performing this work should be
aware of and comply with all Johnson Controls, national, state and local safety and environmental regulations while
carrying out this work. Before attempting to work on any equipment, the individual should be thoroughly familiar
with the equipment by reading and understanding the associated service literature applicable to the equipment. If
you do not have this literature, you may obtain it by contacting a Johnson Controls Service Ofce.
Should there be any question concerning any aspect of the tasks outlined in this bulletin, please consult a
Johnson Controls Service Ofce prior to attempting the work. Please be aware that this information may be time
sensitive and that Johnson Controls reserves the right to revise this information at any time. Be certain you are
working with the latest information.
219
REV
Supersedes SI0270 (818)
Question and Answer IconNeed help?

Do you have a question about the Johnson Controls YORK PYT Series and is the answer not in the manual?

Johnson Controls YORK PYT Series Specifications

General IconGeneral
TypeInverter
SeriesPYT
Compressor TypeScroll
RefrigerantR410A
DimensionsVaries by model
WeightVaries by model

Summary

GENERAL

EXTERNAL PIPING COMPONENTS FOR ALL PYT MODEL DRIVES

FLUSHING PROCESS FOR PYT MODEL DRIVES

SUPPORTING DOCUMENTS

Lists required MSDS sheets and service manuals for the PYT drive coolant flushing process.

STEP 1: Draining The System (All PYT Model Drives)

Details draining the coolant loop from PYT model drives, covering safety, disposal, and heat exchanger valve operation.

STEP 2: Flushing Process (All PYT Model Drives)

Outlines the multi-cycle flushing procedure for PYT model drives, including electrical connections and fluid handling.

STEP 3: Fill Procedure (All PYT Model Drives)

Explains the process of filling the coolant loop for PYT model drives, emphasizing slow addition to minimize foaming.

EXTERNAL PIPING COMPONENTS FOR ALL HYP MODEL DRIVES

FLUSHING PROCESS FOR HYP MODEL DRIVES

SUPPORTING DOCUMENTS

Lists required MSDS sheets and service manuals for the HYP drive coolant flushing process.

STEP 1: Draining The System (HYP0490, HYP0744, HYP0774 Model Drives with Air-cooled Input Inductors)

Details draining the coolant loop for HYP0490, HYP0744, HYP0774 models with air-cooled input inductors.

Draining the System (HYP0490 Mod B, HYP0612, HYP0730, HYP1100, HYP1278 and HYP1300 Model Drives)

Provides draining steps for HYP Mod B, HYP0612, HYP0730, HYP1100, HYP1278/HYP1300 models.

STEP 2: Flushing Process (All HYP Model Drives)

Outlines the multi-cycle flushing procedure for all HYP model drives, using coolant pumps and OptiView panel.

STEP 3: Fill Procedure

Details the fill procedure for the HYP0744 model drive, including pump operation and reservoir level checks.

The following fill procedure applies ONLY to HYP0490, HYP0612, HYP0774, HYP1100 and HYP1278;HYP1300 model drives.

Explains the fill procedure for HYP0490, HYP0612, HYP0774, HYP1100, HYP1278/HYP1300 models.