| Frequency | 433MHz |
|---|---|
| Model | M2AP01 |
| Power Supply | DC 12V |
| Operating Temperature | -10°C ~ +55°C |
| Range | 100m |
Describes installation for MusterWire LHD systems using heat detection wire.
Describes installation for LOP systems using pressure transducers.
Configures relay contacts and system type (LOP/LHD) via DIP switches.
DIP switches 1-3 set shutdown delay time from 0 to 36 seconds.
DIP switches 4-5 are reserved for future or custom applications.
Connects panel to transducer/valve, is polarity sensitive.
Connects panel to LHD wire and manual stations, uses EOL resistor.
Connects to panel relay terminals for fire detection and external alarms.
Connects to panel relay terminals for machine shutdown after fire delay.
Discusses factors affecting battery life and expected duration.
Describes functions like reset, isolation, data logging, and firmware updates via the data port.
Describes Isolated, Standby, Fault, and Fire modes of panel operation.
Explains panel LEDs, Dim function, Buzzer, and Test button functionality.
Describes the relay test mode activated by the TEST button in Isolated mode.
Briefly pressing the TEST button tests buzzer and LEDs in Standby mode.
Details Replace Battery, Over/Under Pressure, and System Fault indicators.
Clears latched faults and tests all circuits in Fault Mode.
Allows silencing the alarm after shutdown sequence in Fire Mode.
Procedure to exit Fire mode and release the shutdown relay for MusterWire LHD systems.
Procedure to exit Fire mode and release the shutdown relay for LOP systems.