DESCRIPTION
INSTALLATION
Check list during installation of the pool heat pump
Install the bypass connection for incoming and outgoing water.
The unit must be connected to the mains supply via a residual current device with a tripping current
of ≤ 30 mA.
Note that rotating parts give off some noise. Remember this when positioning the pool heat pump.
It is extremely important that the pool heat pump has a good air supply and it is therefore
inappropriate to build in the pool heat pump and restrict the air flow.
Make sure there is free flow of air at least 4 metres in front of the heat pump in the direction of the
exhaust air.
Make sure there is sufficient room for the pool heat pump to facilitate installation and maintenance.
At least 30 cm of clearance above the heat pump and 60 cm on the sides. The rear air inlet on the
unit must not be closer than 30 cm to the wall.
Make sure that the pool heat pump is positioned on a strong and stable base.
Front
Top