EasyManua.ls Logo

JUMO LOGOSCREEN 700 - Repeat Instructions; FOR Instruction; WHILE Instruction

JUMO LOGOSCREEN 700
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
4 Electrical connection
Digital input DC 0/24 V
or
digital output DC 0/24 V
(individually switchable),
auxiliary voltage supply DC 24 V
Note regarding analog(HI)/digital op-
tion:
Auxiliary voltage supply and digital
outputs together deliver max. 50 mA
per slot (at 24 V).
Example: potential-free contact on
digital input/output 13 (as input) and
+24 V (auxiliary voltage)
Analog(HI)/digital option
(order code 2):
6.5 / Digital input/output 13
6.6 / Digital input/output 14
6.7 / Digital input/output 15
6.8 / Digital input/output 16
6.9 / +24 V
6.10 / GND
12.5 / Digital input/output 17
12.6 / Digital input/output 18
12.7 / Digital input/output 19
12.8 / Digital input/output 20
12.9 / +24 V
12.10 / GND
18.5 / Digital input/output 21
18.6 / Digital input/output 22
18.7 / Digital input/output 23
18.8 / Digital input/output 24
18.9 / +24 V
18.10 / GND
Example: external voltage on digital
input/output 13 (as input) and GND
Example: external relay on digital in-
put/output 1 (as output) and GND
(max. 40 mA per output, max. 50 mA
in total, see note in the "Version" col-
umn)
Version Terminals and connection symbol Connection element.terminal /
assignment
12345678
+
-
910
12345678
+
-
910
U
x
24 V
-
+
12345678
+
-
910
I
max
= 40 mA