UDP commands
9 / 12
"Enable user" = Enable condition via UDP.
"Max curr" = Current preset value via Control pilot in milliampere.
"Max curr %" = Current preset value via Control pilot in 0,1% of the PWM value
"Curr HW" = Highest possible charging current of the charging connection.
Contains device maximum, DIP-switch setting, cable coding and
temperature reduction.
"Curr user" = Current preset value of the user via UDP; Default = 63000mA.
"Curr FS" = Current preset value for the Failsafe function.
"Tmo FS" = Communication timeout before triggering the Failsafe function.
"Curr timer" = Shows the current preset value of currtime.
"Tmo CT" = Shows the remaining time until the current value is accepted.
"Setenergy” = Shows the set energy limit.
"Output" = State of the output X2.
"Input" = State of the potential free Enable input X1.
When using the input, please pay attention to the information
in the installation manual.
"Serial" = Serial number
"Sec" = Current system clock since restart of the charging station.
report 3
{
"ID": "3",
"U1": 230,
"U2": 230,
"U3": 230,
"I1": 99999,
"I2": 99999,
"I3": 99999,
"P": 99999999,
"PF": 1000,
"E pres": 999999,
"E total": 9999999999,
"Serial": "15017355",
"Sec": 4294967296,
}
"ID" = ID of the retrieved report.
"U1"|"U2"|"U3"| = Current voltage in V.
"I1"|"I2"|"I3"| = Current current value of the 3 phases in mA.
"P" = Current power in mW (Real Power).
"PF" = Power factor in 0,1% (cosphi)
"E pres" = Power consumption of the current loading session in 0,1Wh;
Reset with new loading session (state = 2).
"total" = Total power consumption (persistent) without current loading
session 0,1Wh; Is summed up after each completed charging
session (state = 0).
"Serial" = Serial number