Operation Manual Supply Unit SO CM-P BG1+2
ID no.: 1400.201B.5-00     Date: 02/2020
 
Key: 
Lg = Sum of the cable length for all axes connected [m]
Cx= Permissible total leakage capacitance of the mains lter (see table) [nF]
Cm= Sum of the parasitic capacitances in all motors connected [nF]
Ck = Capacitance of the motor cable used in [nF/m]
Example:
The SO CM system features the possibility of operating up to 24 axes on one supply 
unit. Selected mains lter is in EMCxx.600. 
Due to the capacitance contributed by the motors of 240nF (24x10nF), a total cable 
length of Lg = (402nF-240nF)/0.47nF/m = 344m is permissible. 
That is an average per axis of 14.3 m on a "600m lter". 
A.7.2  Selection of the mains lter taking into account the cable 
and motor leakage capacitances 
The effect of the mains lter is in general limited by the sum of all the leakage 
capacitances in the components connected to the SO CM. This parasitic capacitance 
is primarily determined by the motor cables connected. The capacitances in motors 
connected form a further factor that cannot be ignored. 
Therefore, typical application scenarios were assumed for the development of the lters 
and the capacitances of KEBA motor cables and motors used as the basis to produce 
typical total capacitances for which the lters were designed. For KEBA components the 
following applies: 
KEBA cables have a value of 0.47nF/m 
KEBA motors have a value less than or equal to 10nF 
For the 600 m lter variant, an application with 12 motors each with a cable length of 
50m is assumed for the design. With the above data, there is a total capacitance of  
12 x 10 nF + 12 x 50 m x 470 pF/m = 402 nF. The total leakage capacitances for the 
other mains lters are found similarly. 
Overview of the permissible leakage capacitances for the mains lters 
Filter type
Permissible total leakage 
capacitance Cx [nF]
Max. cable length that can be 
connected for 12 axes [m]
EMCxx.120 176 120
EMCxx.240 261 300
EMCxx.600 402 600
Table E.11  Total leakage capacitances on mains lters
Detailed consideration is necessary in applications with a larger number of axes or long 
motor cables. Detailed consideration is also necessary if cables from other suppliers are 
used and these cables are not designed to have low capacitance, and if motors from 
other suppliers or special motors are used.
As the basis for the estimation of the permissible total cable length, use:
Lg = (Cx – Cm) / Ck