1 Electrical installation
Operation Manual Supply Unit SO CM-P BG1+2
ID no.: 1400.201B.5-00 Date: 02/2020
Electrical installation
4.8 AC mains connection, 24 V switched-
mode power supply
The mains connection on X7 supplies the integrated 24 V switched-mode power supply.
These 24 V DC supply the entire axis group control supply via busbars.
4.8.1 Connector specication
Des. Term. Specication Connection
X7
Line IN Aux
L2
x 2 x 400-480 V AC
x Approx. 2.5 A current
consumption
x Connection cross-section:
6 mm
2
max.
X7
L2
L1
n.c.
n.c.
L1
For layout see Figure 4.8 and Figure 4.9
Table 4.7 Specication, mains connection switched-mode power supply X7
4.8.2 Fuses
For compliance with device safety as per EN61800-5-1, use mains fuses of utilisation
class gG that disconnect the device from the mains in the event of a fault.
Terminal Device Fuse
X7/L1, L2 SOCM-P.0004.x, SOCM-P.0010.x (BG1) 2 x 6 A (gG)
X7/L1, L2 SOCM-P.0022.x (BG2) 2 x 6 A (gG)
See also connection example in Chapter 4.15.1
Table 4.8 Mains fuses for 24 V switched-mode power supply (X7)
NOTE:
The same switched-mode power supply is installed in supply unit BG1 and in
BG2. The technical data are therefore identical.
4.7.2 Operation of the ServoOne CM-P on IT system:
Operation is possible:
y For three-phase supply with 3 x 230 V
y Compliance with the EMC Directive 2014/30/EU must be ensured by the user!
NOTE:
In this operation mode, the declaration of conformity,
CE acceptance and all safety-related approvals are void.
Operation is not allowed:
y For three-phase supply with 3 x 400 V or 3 x 480 V
CAUTION! Damage to the device due to incorrect operation!
Operation with 400/480 V supply voltage is not allowed!
If there is an earth fault the voltage is approx. twice as high. Clearances and creepages to
EN61800-5-1 are no longer maintained. The device may be destroyed in the process.