What to do if KEHUA TECH Measuring Instruments UPS has no output when there is no mains?
- EEric CarrollAug 13, 2025
If your KEHUA TECH Measuring Instruments UPS isn't providing output when mains power is unavailable, several factors could be responsible. First, check the battery for faults or significant damage. Then, verify the charger is functioning correctly to ensure the battery is adequately charged. Also, make sure the battery wires are securely connected and the wire terminals are in good condition. Ensure the battery breaker is closed. Finally, if the UPS was previously overloaded, restart it after resolving the overload condition to take it out of bypass output status.