Info!
Following gures are delivered with protection type IP 55:
21002015CH I 21003015CH I 21004015CH
21412015CH I 21413015CH I 21414015CH
1.
2.
Metallic parts of the building, to which the wall cabinet belongs, have
to be earthed.
The cross section of the wire is half the cross section of the main earth
wire of the building, or at least 6 mm².
If fire protection lagging is necessary
Insert fire protection lagging into the masonry recess.
Insert the cabinet (1).
* A hole of ≥ Ø 27 mm is required for the frost-proof outer fitting (3).
The pre-stamped hole in the built-in wall cabinet (1) can be used as
a template. A slope of max. 2 % must be maintained from inside to
outside.
Danger!
Earthing
Connect the earthing with the
intended screws at the upper
part of the wall cabinet and
the door (All metallic parts are
earthed by this).
2
Installation of built-in wall cabinet
Provide the power supply
- Note FI fuse:
Nominal fault current ≤ 0.03 A
and Connection current ≤ 32 A
- Protection type IP 44
When fitting the built-in wall cabinet (1), take into account the later
wall construction of the outer façade. Max. possible compensation by
the trim frame: 20 mm!
Insulation without fire protection jacket.
Insulaiton on the back side is recommended (e.g. expanded polystyrene).
Insert rear insulation.
Insert the cabinet into the opening and fix it.
If necessary, drill four holes and attach the cabinet (1) to the
rear wall using the four attachment screws provided (2)
(four holes, Ø 8 mm).
1.
2.
3.