EasyManua.ls Logo

Ketotek KT4000 - User Manual

Default Icon
2 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Ketotek Technology Inc. www.cnketotek.com
1
KT4000 Temperature Controller
Operating Manual
1. Overview
KT4000 is easy-to-use and reliable dual relay output
temperature controller. It can be used as automatic
temperature control system for various electric appliances.
2. Mail Features
Acrylic panel, plastic-steel socket shell
Control heater and cooler to adjust temperature.
One setpoint and one differential .Very easy to set .
Alarm when temp exceed temperature limit or sensor error
Autosave the program setting when power down.
2. Specifications
Power Supply: 110Vac±15% , 50/60hz
Temperature control range:-19.9~199.9
Return difference :1.0~30
Temperature control accuracy: ±1
Screen resolution : 0.1
Temperature sensor : NTC Waterproof sensor 2m/6.56ft
Output Relay Contact Capacity: 16A, 100-240Vac
3. Product picture
Left heating socket connect with heater.
Right cooling socket connect with refrigerator/cooler.
Dimensions:
Control panel: 92x50x17mm (3.6x1.97x0.67inch)
Socket: 208x66x40mm (8.2x2.6x1.57inch)
4. Key Instruction
: Cool output indicator. When this light on, cooling
socket have power output. Cooler start to work ; When the
light flash, cooling socket output delay .
: Heat output indicator. When this light on, heating
socket have power output. Heater start to work.
: Temperature alarm.When the temperature exceed the
limit range of AL~AH, this light flash and buzzer alarm.
Operation
In normal working status, the screen display RT(real time
temperature detected from sensor). press once. it display
temperature set value LS(see code table). press once. it
display differential value Ld.
The screen backlight will closed after 10minutes
no-operation.
In normal working status, press SET for 3s to enter setting
parameter mode. The screen display LS. Press or to
increase or decrease LS value. Then press SET to go into
next code Ld. Press or to adjust value.
Using the same way to set code value from LS~CA one by
one (see code table). After finishing all setting, press SET
for 3seconds to save the setting and return to normal
display. If no key operation after finishing all settings
within 30seconds, the system won’t save modified
parameter and back to normal display.
Restore factory default setting:
In normal working status, press and together for 3s.
The screen will display FF and restore all code to default
factory setting.
Code Table:
Basic setting
For example,we use this thermostat to control temperature
of a reptile incubator. Heating socket connect with
light.Cooling socket connect with fan.
Only need to set LS=80 . No need to change other
parameters.
Fan works when temperature
84
. Fan stop working
when temperature <80.
Light works when temperature<76 . Light stop
working When temperature
80
.
Advanced Setting.
Set the required temperature LS. Then set Ld PL AH AL
CA. (AH>LS+Ld , AL<LS-Ld). The controller will work
in following status:
Code
Function
Set Range
Default
LS
Temperature Set Value
-19.9~199.9
68
Ld
Differential Value
1.0~30
4
PL
Set cooling delay output
0~10minutes
0
AH
Alarm high limit
-19.9~199.9
199.9
AL
Alarm low limit
-19.9~199.9
-19.9
CA
Temperature Calibration
-19.9~19.9
0
Question and Answer IconNeed help?

Do you have a question about the Ketotek KT4000 and is the answer not in the manual?

Summary

Overview of KT4000 Temperature Controller

KT4000 Controller Description

Describes the KT4000 as an easy-to-use, reliable dual relay output temperature controller for electric appliances.

Main Features of KT4000

Construction and Control

Features an acrylic panel, plastic-steel shell, and controls both heater and cooler for temperature adjustment.

Simple Operation Settings

Offers one setpoint and one differential for very easy setup and operation.

Alarm and Error Handling

Includes alarms for exceeding temperature limits or sensor errors, and autosaves settings on power loss.

KT4000 Specifications

Power and Temperature Specs

Details power supply (110Vac), temperature control range (-19.9~199.9°F), and return difference (1.0~30°F).

Accuracy, Resolution, and Sensor

Specifies ±1°F accuracy, 0.1°F resolution, and NTC waterproof sensor (2m/6.56ft).

Output Relay Capacity

States the output relay contact capacity is 16A at 100-240Vac.

Product Picture and Key Instructions

Product Visuals and Dimensions

Shows product images and provides dimensions for the control panel and socket.

Indicator Lights and Operation Modes

Explains indicator lights and describes normal operation, setting parameters, and saving settings.

Factory Reset and Parameter Codes

Details how to restore factory defaults and lists code table functions, ranges, and defaults.

Setting Examples and Advanced Options

Provides basic and advanced setting examples for temperature control, including delays and alarms.

Operational Logic and Error Handling

Cooler and Heater Logic

Explains the logic for cooler and heater activation/deactivation based on temperature setpoints (LS, Ld).

Cooling Delay (PL) Function

Describes the function of the cooling delay output (PL) where the cooler does not work immediately.

High;Low Limit Alarms (AH, AL)

Details how high (AH) and low (AL) temperature limits trigger alarms and stop outputs.

Temperature Calibration (CA)

Explains how to use the CA value to calibrate the measured temperature against the actual temperature.

Troubleshooting Error Codes

Addresses error codes HHH (short circuit) and LLL (open circuit) for the temperature sensor.

Warnings and Warranty Information

Important Warnings

Warns about keeping the controller away from water and recommends power limits for different load types.

Product Warranty

Outlines the 12-month warranty period and commitments for defective products (repair, replace, refund).

Overview

The KT4000 is a user-friendly and dependable dual-relay output temperature controller designed for automatic temperature control in various electrical appliances. It features an acrylic panel and a plastic-steel socket shell, allowing it to control both heating and cooling elements to maintain a desired temperature. The device simplifies temperature management with a single setpoint and differential, making it very easy to configure. Additionally, it includes an alarm function that activates when the temperature exceeds predefined limits or if a sensor error occurs. All program settings are automatically saved even after a power down, ensuring continuous operation without loss of configuration.

In its normal operating state, the screen displays the real-time temperature detected by the sensor. A single press of the "SET" button will show the temperature set value (LS), and another press will display the differential value (Ld). To conserve energy, the screen backlight automatically turns off after 10 minutes of inactivity.

For more advanced configuration, pressing and holding the "SET" button for 3 seconds enters the setting parameter mode, where the screen displays "LS." Users can adjust the "LS" value using the "UP" or "DOWN" buttons. Subsequent presses of "SET" will cycle through other parameters like "Ld," allowing for further adjustments. This method is used to set all code values from "LS" to "CA" as listed in the code table. Once all settings are complete, pressing and holding "SET" for 3 seconds saves the configuration and returns the device to its normal display. If no button is pressed for 30 seconds after entering the setting mode, the system will not save any modified parameters and will revert to the previous settings.

The KT4000 also offers a convenient way to restore factory default settings. In normal working status, simultaneously pressing the "UP" and "DOWN" buttons for 3 seconds will display "FF" on the screen, indicating that all code values have been reset to their default factory settings.

The device provides clear visual indicators for its operational status. A "COOL" indicator light illuminates when the cooling socket is active, supplying power to a cooler. If this light flashes, it signifies a delay in the cooling output. Similarly, a "HEAT" indicator light turns on when the heating socket is active, providing power to a heater. An "ALARM" indicator flashes, accompanied by a buzzer, when the temperature exceeds the alarm high limit (AH) or falls below the alarm low limit (AL), or in the event of a sensor error.

For basic setup, consider an example where the thermostat is used to control the temperature of a reptile incubator, with the heating socket connected to a light and the cooling socket connected to a fan. In this scenario, only the "LS" (temperature set value) needs to be set, for instance, to 80°F, with no other parameters requiring adjustment. Under these settings, the fan will activate when the temperature reaches 84°F or higher and stop when it drops below 80°F. Conversely, the light will turn on when the temperature falls below 76°F and turn off when it reaches 80°F or higher.

For advanced settings, after setting the desired "LS" temperature, users can configure "Ld" (differential value), "PL" (cooling delay output), "AH" (alarm high limit), "AL" (alarm low limit), and "CA" (temperature calibration). It's important to ensure that "AH" is greater than "LS + Ld" and "AL" is less than "LS - Ld" for proper operation.

The cooling delay output (PL) feature is particularly useful. If "PL" is set, the cooler will not activate immediately in cooling mode. Instead, the "COOL" indicator will flash, and the cooler will delay its operation by the specified "PL" time.

The alarm high/low limit settings (AH, AL) provide an essential safety feature. If the measured temperature reaches or exceeds "AH," a high-temperature alarm will be triggered, with the buzzer sounding and the "ALARM" indicator flashing. This alarm will persist until the temperature drops below "AH" or any key is pressed. Similarly, if the measured temperature falls to or below "AL," a low-temperature alarm will activate, with the buzzer and flashing "ALARM" indicator continuing until the temperature rises above "AL" or a key is pressed.

The temperature calibration (CA) function allows users to correct any discrepancies between the measured temperature and the actual temperature. By setting a "CA" value, the device can align the displayed temperature with the true temperature, where the corrected temperature equals the measured temperature plus "CA."

Regarding maintenance and troubleshooting, if the heater or cooler fails to activate when the specified temperature is reached, users should check the "Ld" value, verify the sensor placement, and ensure that "PL" is not set, as a delay in cooling output could be the cause. If the screen displays "HHH" or "LLL," it indicates a sensor issue. "HHH" signifies a short circuit in the temperature sensor, while "LLL" indicates an open circuit. In either case, the buzzer will alarm with a flashing "ALARM" indicator, which cannot be stopped by pressing any key. The solution is to inspect or replace the sensor.

It is crucial to note that while the sensor probe is waterproof, the controller itself is not. Therefore, the controller should be kept away from water. To ensure optimal performance and prevent overloading, each output socket utilizes a high-quality 16A relay. For resistive loads such as heating rods, heating pads, or electric water heaters, the maximum recommended power is 1100W. For inductive loads like compressors or pumps, the maximum recommended power is 275W.

The product comes with a 12-month warranty from the date of purchase. In the event of a defect due to qualified product problems, the company commits to repair, replace, or refund the device. For technical support or customer service, users can contact info@cnketotek.com.

Ketotek KT4000 Specifications

General IconGeneral
Display ColorRed
Control OutputRelay Output
DisplayLED
Control Accuracy0.1°C
Power SupplyAC 110V-220V
Control AlgorithmPID

Related product manuals