Chapter 6: Preventive maintenance and testing 
 
P/N 3101890-EN • REV 006 • ISS 21JUN18  115 
  Test  Test methods 
  Visual inspection  Inspect the equipment for any visible signs of damage or 
other changes that may adversely affect performance. 
Initial and Reacceptance  1.  Verify that the remote annunciator indicates open, short, 
and ground faults while testing the panel. 
2  Very that all controls and indicators are working. 
3.  If LEDs are configured, verify the indicators by activating 
the points correlated to the LED. 
4.  Disconnect the RS-485 line and verify that a trouble 
message is displayed on both the panel and the remote 
annunciator. 
  Visual inspection  1.  Verify that the detector’s green LED flashes. 
2.  Inspect the equipment for any visible signs of damage or 
other changes that may adversely affect performance. 
Clean if necessary.  
Initial and Reacceptance  1. 
Remove the detector from its base. Verify that the control 
panel displays a trouble message that correctly identifies 
the detector. 
2.  Activate the detector. Verify that the detector’s red LED 
flashes and the control panel displays an alarm message 
that correctly identifies the detector. 
3.  If the detector is installed in a relay base, verify the 
correct operation of the relay. 
4.  Run a Device Maintenance Report on all the smoke 
detectors in the system. Verify that all sensitivity levels 
fall within acceptable limits. Keep a printed copy for your 
records. 
Annual  1.  Activate the detector. Verify that the detector’s red LED 
flashes and the control panel displays an alarm message 
that correctly identifies the detector. 
2.  If the detector is installed in a relay base, verify the 
correct operation of the relay. 
3.  Run a Device Maintenance Report on all the smoke 
detectors in the system. Verify that all sensitivity levels 
fall within acceptable limits. Keep a printed copy for your 
records.