EasyManua.ls Logo

Kidde VM-1 - Page 124

Kidde VM-1
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 6: Preventive maintenance and testing
116 P/N 3101890-EN • REV 006 • ISS 21JUN18
Component
Test Test methods
Heat detectors
Visual inspection 1. Verify that the detector’s green LED flashes.
2. Inspect the equipment for any visible signs of damage or
other changes that may adversely affect performance.
Clean if necessary.
Initial and Reacceptance Caution: Directing heated air at a single point may
permanently damage the heat detector. Wave the hair blower
slowly back and forth approximately 1 in. from the heat entry
slots.
1. Remove the detector from its base. Veri
fy that the control
panel displays a trouble message that correctly identifies
the detector.
2. Activate the detector using a commercial grade (1200 t
o
1500
W) hair blower. Verify that the detector’s red LED
flashes and the control panel displays an alarm
message
that correctly identifies the detector.
3. If the detector is installed in a relay base, verify the
correct operation of the relay.
Annual Caution: Directing heated air at a single point may
permanently damage the heat detector. Wave the hair blo
wer
slowly back and forth approximately 1 in. from the heat entry
slots.
1. Activate the detector using a commercial grade (1200 t
o
1500
W) hair blower. Verify that the detector’s red LED
flashes and the control panel displays an alarm message
that correctly identifies the detector.
2. If the detector is installed in a relay base, verify the
correct operation of the relay.
Duct detectors
Visual inspection Inspect the equipment for any visible signs of damage or
other changes that may adversely affect performance.
Initial and Reacceptance
Activate the equipment. Make sure the control panel correctly
identifies the device.
Semiannual
Activate the equipment. Make sure the control panel correctly
identifies the device.
Fire alarm boxes
Visual inspection Inspect the equipment for any visible signs of damage or
other changes that may adversely affect performance.
Initial and Reacceptance
Activate the equipment. Make sure the control panel correctly
identifies the device.
Semiannual Activate the equipment.
Make sure the control panel correctly
identifies the device.

Other manuals for Kidde VM-1

Related product manuals