Appendix C: Programming options
P/N 3101890-EN • REV 006 • ISS 21JUN18 205
Programmable feature or option
Permitted
in UL 864? (Y/N)
Possible
settings
in UL 864
AND group member device types, Activation
event: Q1
- Alarm
Y GENALARM
SMOKE
SMOKEVFY
HEAT
PULL
STAGEONE
STAGETWO
WATERFLOW
COALARM
COSUPERVISORY
GENALARM
SMOKE
SMOKEVFY [9]
HEAT
PULL
STAGEONE [9]
STAGETWO [9]
WATERFLOW
COALARM
COSUPERVISORY
AND group device activation count
Y 1 to 255 1 to 255 [10]
Input modules: Personality code 18
N N/A N/A
-IO(-MIO) modules: Personality codes
N N/A N/A
N Latching
Nonlatching
N/A
N Latching Nonlatching N/A
N N/A N/A
[1] Allowed only when the supervising station supervises the telephone line and annunciates fault conditions
within 200 seconds
[2] Allowed only on control panels that transmit trouble event signals off premises
[3] Allowed only with monitor device types and switches
[4] Allowed only if the user route includes the control panel
[5] Allowed only on nonrequired remote annunciators
[6] Allowed only when setting does not prevent the activation or transmission of alarm or supervisory signals
within 10 seconds or trouble signals within 200 seconds
[7] When priorities are used, alarm events must have a higher priority than supervisory and trouble events
[8] Not allowed in Zone groups that are used to initiate the release of extinguishing agent or water
[9] Not allowed in AND groups that are used to initiate the release of extinguishing agent or water
[10] A minimum device activation count of 2 is required if the AND group or matrix group is used to initiate the
release of extinguishing agents or water
[11] If only one type of passive communication is available at the protected premises, there shall be two channels
provided. Separate paths throughout the protected premises and through any common carrier or third party
communications network to the fire signal receiving center shall be provided for each communication
channel.