Appendix C: Programming options
204 P/N 3101890-EN • REV 006 • ISS 21JUN18
Programming options
For programming instructions, refer to the VM-CU Help.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES:
This product incorporates field-programmable software. In order for the product to comply with the requirements
in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features
or options must be limited to specific values or not used at all as indicated below.
Programmable feature or option
Permitted
in UL 864? (Y/N)
Possible
settings
in UL 864
Telephone line supervision
Y No
Yes
Yes
Y No
Yes
No [1]
Yes [11]
Resound Y 00:00:00
to 99:59:59
00:00:00 [2]
to 24:00:00
Y Disabled
01:00 to 45:00
01:00 to 03:00
Y All Cabinets
No Cabinets
User defined routes (1
to 15)
All Cabinets
No Cabinets [3]
User defined routes
(1 to 15) [4]
isplay filtering: Alarm,
Supervisory, and Trouble options
Y Enabled
Disabled
Enabled
Disabled [5]
correlations) Y 0 to 65,535 seconds
[6]
Y 0 to 56 seconds 0 to 44 seconds
al silence Y 0 to 60 minutes 3 to 30 minutes
Y 0 to 3 minutes 3 minutes
CMS event reporting priority (programmed in
correlations)
Y 1 to 255 1 to 255 [7]
CMS activate and restore messages
(programmed in correlations)
Y Send on activation
Send on restoration
Activation and
restoration triggers
must match the
message type
Zone group member device types
Y GENALARM
SMOKE
SMOKEVFY
HEAT
PULL
STAGEONE
STAGETWO
WATERFLOW
COALARM
COSUPERVISORY
GENALARM
SMOKE
SMOKEVFY [8]
HEAT
PULL
STAGEONE [8]
STAGETWO [8]
WATERFLOW
COALARM
COSUPERVISORY