Chapter 3: Operating instructions
32 P/N 3101890-EN • REV 006 • ISS 21JUN18
Output of the disable state
Upon entering the disable state, the control panel:
• Activates the first trouble pseudo point
• Activates the first disable pseudo point
• Changes the active state for the point that signaled the disable event
Indication of the disable state
To indicate it is in the disable state, the control panel:
• Sounds the panel buzzer
• Turns on the Disable LED
• Flashes the Trouble LED
• Displays an event message in the Trouble Queue for the point that signaled the disable event, provided there
are no higher priority events
Supervisory state
The control panel enters the supervisory state when a point signals a supervisory event.
Output of the supervisory state
Upon entering the supervisory state, the control panel:
• Activates the common supervisory contacts on the VM-CPU
• Activates the first supervisory pseudo point
• Changes the active state for the point that signaled the supervisory event
Indication of the supervisory state
To indicate it is in the supervisory state, the control panel:
• Sounds the panel buzzer
• Flashes the Supervisory LED
• Displays an event message in the Supervisory Queue for the point that signaled the supervisory event,
provided there are no higher priority events
If the active point is a supervisory zone and a control-indicating module is installed, the control panel also flashes
the zone’s active LED on the module.
Trouble state
The control panel enters the trouble state when a point signals a trouble event.
Output of the trouble state
Upon entering the trouble state, the control panel:
• Activates the common trouble contacts on the main board
• Activates the first trouble pseudo point
• Changes the active state for the point that signaled the trouble event