Page
9
of
14
King Pigeon Hi-Tech. Co., Ltd. Ver 2.4
Temperature&Humidity&Analog
&Voltage&Power Status Alarm
Disarmed stands for while alarm occurrence, will not send SMS
or dial to alert users.
5) Setup Authorized User number (Total 10 authorized number, each number max 21 digits.)
When alarm/Recovery occurrence, the RTU502x will send predefined SMS to the 1st ~5th numbers, and
send SMS also dial 6th ~10th numbers, till any one answer it or cycle dial 3 times.
Just dial from Authorized User number, the RTU502x will reject at the first
“
Ring
”
, no communication cost,
and then return the current temperature, humidity, power voltage by SMS.
The 1th number can also receive daily report SMS.
PWD+A+x+T+y
(x= 01~10,must be 2 digits,stands for series number)
(y stands for phone number,max 21 digits,supports add country code,e.g.
+86 or 0086)
e.g.: 1234A03T008613570810254 to setup 008613570810254
as the 3
rd
number.
1: ---
2: ---
3: 13570810254
4: ---
6) Setup Alarm Parameter 1
PWD+AIN+x+T+y
x=1,2,3;1 stands for temperature or analog input,2 stands for
humidity,3 stands for voltage(below x are the same)
y stands for channel name,max 20 characters
Temperature/AIN:y
Humidity:y
Voltage:y
PWD+AINR+x+L+y+H+z+#
y stands for low threshold value;z stands for high threshold value,if
y=z,will not alarm
RTU5023 valid temperature range:-400~800(stands for 40℃~80℃);
RTU5026 valid temperature range:-550~1250(stands for -55℃
~125℃);
Humidity valid range:0~100(stands for 0%RH~100%RH);
Voltage valid range:0~370(stands for 0V~37V);
Analog signal range:-32767~32767(stands for -3276.7~3276.7);
When sending SMS command to setup,except humidity should be
setup according to actual value,the temperature, voltage and analog
value should be setup at 10 multiples of actual value.
If setup by APP, all of them can be setup according to actual value.
Recommended to use the APP for setting.
E.g.1234AINR1L-120H356# to setup temperature low threshold as
-12.0℃,high threshold as 35.6℃;
1234AINR2L10H90# to setup humidity low threshold as 10%RG,high
threshold as 90%RH
Temperature/AIN:
low:y,High:z.
Humidity:
Low: y,High: z.
Voltage:
Low: y,High: z.