4
PARAMETER’S TABLE
No
code
description
min
max
Μ.Μ.
INDUSTRIAL FACTORY SETTINGS OF THE CABINET
Upright chiller
R134a
Upright chiller
R290
Upright freezer
with stainless
door R404A
Upright freezer
with stainless
door R290
Upright freezer
with glass door
R404A
Upright freezer
with glass door
R290
Refrigerated
counters
Saladette
Program 33
Program 38
Program 36
Program 34
Program 37
Program 35
Program 31
Program 32
1
SΡo
SET POINT: room temperature setting
LSP
HSP
°C/°F
0.0
0.0
-20.0
-22.0
-18.0
-18.0
0.0
3.0
2
ALo
Low alarm room threshold
-50.0
150
°C/°F
-5.0
-5.0
-25.0
-25.0
-22.0
-22.0
-5.0
-5.0
3
i
High alarm room threshold
-50.0
150
°C/°F
15.0
15.0
0.0
0.0
0.0
0.0
15.0
15.0
4
dr1
Time between two successive defrost
1
100
hours
4
4
5
7
5
7
4
4
5
Cod
Access code to the following parameters Cod = 22.
0
255
-
22
22
22
22
22
22
22
22
6
diF
Differential of room temperature SPo (thermostat delay)
0.1
25.5
°C/°F
3.0
3.0
3.0
4.0
3.0
4.0
3.0
3.0
7
dd2
Defrost duration (manual and automatic), where 0 = defrost is
deactivated.
0
120
min
20
20
35
35
35
35
25
25
8
dΡ3
Dripping timer, where the compressor is OFF after defrost
0
15
min
2
2
5
5
5
5
0
0
9
dY4
Display indication during defrost
-02 = indication SPo+diF when room’s temperature is greater than
SPo+diF
-01 = indication dFr when room’s temperature is greater than
SPo+diF
0 = indication of room’s temperature
1 to 40 min = indication dFr from 1 to 40 min counting from the
beginning of defrost
-02
40
min
25
25
35
35
35
35
25
25
10
dE5
Defrost end temperature
with the evaporator’s temperature sensor activated
Automatic and manual defrost does not start if the evaporator
temperature is greater than the defrost end temperature dE5.
In case of evaporator’s sensor malfunction (LF2), there is no check
of defrost end temperature and defrosting is completed after time
adjusted in parameter dd2 elapses.
with the evaporator’s temperature sensor deactivated
Defrost end temperature is the room temperature. Automatic
defrost does not start if the evaporator temperature is greater than
the defrost end temperature dE5.
Manual defrost starts regardless of the room’s temperature and
ends after time adjusted in parameter dd2 elapses.
0.0
100
°CF
20.0
20.0
30.0
30.0
30.0
30.0
20.0
20.0
11
dt6
Type of defrost
0 = electrical (compressor OFF, resistance ΟΝ), if SPo is smaller
or equal than -0.1
o
C defrost occurs using the resistance based on
time adjusted from the parameter dd2, if SPo is greater or equal
than 0
o
C defrost occurs using the fan based on time adjusted from
the parameter dd2.
1 = hot gas (compressor ON, resistance ON)
- - - - - - - - - - - -
Defrost with the evaporator’s temperature sensor activated
Automatic or manual defrost ends either with time adjusted from the
parameter dd2 or with defrost end temperature dE5, whatever
comes first. Automatic or manual defrost does not start if the
evaporator temperature is greater than the defrost end temperature
dE5.
Defrost with the evaporator’s temperature sensor deactivated
Defrost end temperature is the room temperature.
Automatic defrost ends either with time adjusted from the parameter
dd2, or with defrost end temperature dE5, whatever comes first.
Manual defrost starts regardless of the room’s temperature and
ends after time adjusted in parameter dd2 elapses.
0
1
-
0
0
0
0
0
0
0
0
12
AF1
Alarm setting
0 = automatic deactivation, where the alarm stops once the cause
of the alarm disappears.
0
1
-
0
0
0
0
0
0
0
0