1 = manual deactivation, where the alarm indication remains even
if the cause of the alarm disappears and it’s cleared only by
pressing .
In any case by pressing , the buzzer stops and turns on
to state that the cause of the alarm still exists. Muting the alarm
buzzer by pressing once is valid until all alarms disappear.
Time delay in activating “AΗi”, “ΑLo” and the buzzer among them.
This setting does not apply to sensor failure and door alarm.
-01 = deactivate buzzer
0 = immediate buzzer activation
1 to 120 min = delay in buzzer activation
When the cabinet starts for the first time, the buzzer is deactivated
until the last alarm disappears.
Evaporator’s temperature controlling the fan operation during
defrost and normal operation (
parameter οS2 = 1). If the
evaporator’s sensor is deactivated, the parameter does not operate.
For more information check the parameters Ft2 and Fd3.
Evaporator’s fan operation
-01 = continuous function
0 = parallel with the compressor
1 to 15 min = functions at the same time with the compressor and
when the compressor stops, the fan stops after the selected minutes
Fan’s operation during defrost for SPo smaller or equal than -0.1
o
C
0 = OFF and starts with the compressor if the evaporator’s
temperature is smaller than Fo1 – setting applies only with the
evaporator’s sensor activated
1 = ON when the evaporator’s temperature is smaller than Fo1 –
setting applies only with the evaporator’s sensor activated
2 = always ON in both types of defrost (electrical / hot gas)
regardless of the evaporator’s sensor operation
Compressor’s minimum time ON
Compressor’s minimum time OFF
Compressor’s operation in case of room’s sensor malfunction
-01 = compressor OFF
0 = compressor ON while defrost starts based on timer dr1 and
ends based on timer dd2 or temperature dE5, whichever comes
first.1 to 150 min = compressor time ON while defrost starts based
on timer dr1 and ends based on timer dd2 or temperature dE5,
whichever comes first.
Compressor time OFF in case of room’s sensor malfunction
Evaporator’s sensor operation
0 = deactivated sensor
1 = activated sensor
When the sensor is deactivated, by pressing it is displayed
“- - -”.
During defrost and when the sensor is deactivated, the defrost end
temperature dE5 is the room temperature.
Lower setting limit of SPo
Maximum setting limit of SPo
Temperature measurement unit: toggling between °C/°F do not
adjust automatically parameters regarding temperature, the user
must change them manually
0 = °C
1 = °F