EasyManua.ls Logo

Kipor KDE19STA - Default Chapter; Table of Contents

Kipor KDE19STA
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1. Safety Information
2. Parts Name and Control Unit
2.1 Generator fig
2.2 Control Panel
2.3 Breaker
2.4 Fuel Meter
2.5
2.6 AC Three-phase and Single-phase Output Terminals
3. Pre-running Check
3.1 Engine Oil
3.2 Fuel
3.3 Coolant
3.4 Fuel-water Separator
3.5 Battery
4. Start and shut off the engine
4.1 Break-in Period (initial 50 hours)
4.2 Start the Engine
4.3 Stop the Engine
The functions of the digital panel
1
2
2
3
4
4
5
6
7
8
9
11
12
13
14
14
14
16
CONTENTS
38
The conditions of generator rated output:
Altitude: 0 m Ambient temperature: 25 Relative humidity: 30%
Ambient modified coefficient: C (Relative humidity 30%)
Note: When the relative humidity is 60%, the modified coefficient is C-0.01
When the relative humidity is 80%, the modified coefficient is C-0.02
When the relative humidity is 90%, the modified coefficient is C-0.03
When the relative humidity is 100%, the modified coefficient is C-0.04
Counting example:
When the rated power of generator is P =5KW, altitude is 1000m, ambient
N
temperature is 35 , relative humidity is 80%, the rated power of generator is:
P=P (C-0.02) = 5 (0.82-0.02) = 4KW
N
2. Modified coefficient table of ambient condition power
Ambient temperature ( )
Altitude
(m)
0
500
1000
2000
3000
4000
25
1
0.93
0.87
0.75
0.64
0.54
30
0.98
0.91
0.85
0.73
0.62
0.52
35
0.96
0.89
0.82
0.71
0.6
0.5
40
0.93
0.87
0.80
0.69
0.58
0.48
45
0.90
0.84
0.78
0.66
0.56
0.46