Marine Generator Sets
Models:
13.5CCOZ/11CCFOZ
18.5 CCOZ/15CCFOZ
21CCOZ/16.5CCFOZ
18CCFOZ
14CCOZ/11.5CCFOZ
20CCOZ/17.5CCFOZ
24CCOZ/20CCFOZ
1 Phase
and 3 Phase
TP-5592 7/96a
Operation and
Installation Manual

Table of Contents

Questions and Answers

  • I
    imooreSep 10, 2025
    What to do if the starter on my Kohler 13.5CCOZ doesn't work?
    • B
      Billy ArnoldSep 10, 2025
      If the starter on your Kohler Inverter isn't working correctly, begin by cleaning and tightening any loose connections. Also, replace the starter solenoid, replace the start/stop switch, and check the wiring.
  • J
    josephdunnAug 22, 2025
    What causes low output voltage on a Kohler 13.5CCOZ?
    • C
      Chris DavisAug 22, 2025
      If you're experiencing low output or an excessive voltage drop on your Kohler Inverter, try adjusting the governor if the engine speed is too low. If the generator is overloaded, reduce the load.
  • H
    Haley McdonaldAug 25, 2025
    How to fix a Kohler 13.5CCOZ Inverter that won't crank?
    • A
      aunderwoodAug 25, 2025
      If your Kohler Inverter won't crank, possible causes include a weak or dead battery (recharge or replace it), reversed or poor battery connections (check and correct them), a tripped circuit breaker in the controller (reset it), a defective start/stop switch (check and replace if necessary), a defective starter solenoid (check and replace if necessary), or a defective starter (replace/repair as necessary).
  • S
    silvatheresaAug 26, 2025
    What to do if my Kohler 13.5CCOZ cranks but won't start?
    • S
      Scott ScottAug 26, 2025
      If your Kohler Inverter cranks but doesn't start, check these potential issues: * Make sure you're not out of fuel; if so, replenish it. * Check for any fault shutdowns and examine the shutdown switches. * Ensure the fuel shut-off valve is open. * Other possible causes include a defective fuel feed pump (replace it), a clogged fuel filter (service the filter element), or air in the fuel system (bleed the air). Also, consider water or dirt in the fuel system (drain and flush), incorrect fuel type (use the correct type), incorrect crankcase lube oil (use the correct lube oil), or a faulty fuel solenoid (replace it). Finally, check for a clogged air intake (clean or replace it), a faulty ground connection (clean and retighten), or a weak/dead battery (recharge or replace).
  • C
    Caleb JohnsonAug 27, 2025
    How do I troubleshoot a Kohler 13.5CCOZ with no AC output?
    • M
      Maria SandersAug 28, 2025
      If your Kohler Inverter has no AC output, verify the following: * Ensure the circuit breaker is in the ON position; if it's OFF, reset it. * If the circuit breaker tripped due to an overload, reduce the load and reset the breaker. * Confirm the ship-to-shore transfer switch is set to generator power, not OFF or SHORE. * Check if the controller circuit breaker has tripped and reset it if necessary.
  • S
    scottpowersAug 29, 2025
    Why does my Kohler 13.5CCOZ engine start but not continue running?
    • L
      Lisa MaciasAug 29, 2025
      If your Kohler Inverter engine starts but doesn't continue to run after releasing the start switch, it could be due to no generator output voltage (check AC voltage), a defective low oil pressure (LOP) safety shutdown switch (replace it), or a high temperature shutdown (check coolant level). Also, consider defective high exhaust temp. (HET) and/or high water temp. (HWT) safety shutdown switch(es) and replace them if needed.
  • G
    garciaoscarSep 18, 2025
    What could be the reason for engine knocking in my Kohler 13.5CCOZ Inverter?
    • M
      melaniealvarezSep 18, 2025
      If your Kohler Inverter's engine is knocking, the cause might be using the incorrect type of fuel (use correct type of fuel) or air in injectors (bleed air).
  • J
    Justin HillSep 12, 2025
    What causes low lube oil pressure in a Kohler 13.5CCOZ?
    • P
      Pamela ThomasSep 12, 2025
      Low lube oil pressure in a Kohler Inverter can be caused by a low lube oil level (add lube oil), incorrect lube oil viscosity (drain and fill with correct lube oil), or a defective oil pressure switch (replace safety shutdown switch).
  • T
    Traci StricklandSep 8, 2025
    What causes high fuel consumption in a Kohler Inverter?
    • L
      Lisa PatelSep 8, 2025
      High fuel consumption in your Kohler Inverter could be due to several factors: using the incorrect type of fuel (use correct fuel), a clogged or dirty air intake silencer (service air intake silencer), an overloaded engine (reduce load), or fuel leakage (check for leaks at fuel tank, lines, and engine fuel system). Also, check the thermostat and consider the engine temperature.
  • C
    crystal96Sep 5, 2025
    Why is my Kohler Inverter engine operating erratically?
    • S
      Sean DelgadoSep 5, 2025
      If your Kohler Inverter engine operates erratically, consider these potential causes: a clogged air intake (service air intake silencer), stale or bad fuel (replace fuel), a clogged fuel filter (replace fuel filter), an obstructed vent in the fuel tank cap (clean cap in solvent and blow dry), or water, dirt, or air in the fuel system (drain, flush, fill, and bleed air in the system). Also, check the fuel feed pump (replace if defective).

Summary

Safety Precautions and Instructions

Accidental Starting Safety

Procedures to prevent unintended generator set startup.

Battery Safety Guidelines

Guidelines for safe handling and maintenance of batteries.

Engine Backfire and Flash Fire Safety

Safety measures to prevent engine backfire and flash fires.

Exhaust System Safety Precautions

Precautions regarding carbon monoxide and exhaust systems.

Fuel System Safety Measures

Safety measures for handling, storing, and using fuels.

Electrical Safety Warnings

Warnings and precautions related to hazardous voltage and electrical shock.

Heavy Equipment and Hot Parts Safety

Safety considerations for heavy equipment and hot parts.

Moving Parts Safety Guidelines

Guidelines to prevent injury from moving generator set parts.

Reference Material

Pleasurecraft Installation Regulations

Governing regulations and standards for pleasurecraft installations.

Commercial Vessel Installation Regulations

Governing regulations and standards for commercial vessel installations.

Introduction

Service Assistance

Contacting Kohler Service and Support

Information on obtaining sales, service, and technical support.

Routine Service Parts

Specifications

General Specifications- 1-Phase Models

Technical specifications for single-phase generator models.

General Specifications- 3-Phase Models

Technical specifications for three-phase generator models.

Generator and Alternator Features

Details on the generator's design, construction, and alternator components.

Generator Ratings (1-Phase Models)

Performance ratings for single-phase generator models.

Engine Data and Specifications

Key data points and detailed specifications for the generator set's engine.

Controller Features and Operation

Description of the generator set controller's capabilities.

Generator Set Accessories

Available optional accessories for the generator set.

Operation Procedures

Prestart Checklist

Essential checks to perform before starting the generator set.

Generator Set Operation

Procedures for exercising the generator set and understanding controller functions.

Starting and Stopping Procedures

Step-by-step guides for starting, stopping, and using the preheat feature.

Protection and Shutdown Features

Details on circuit protection and engine safety shutdown features.

Remote Control Panels

Information on optional remote start and meter panels.

Scheduled Maintenance

General Maintenance Guidelines

Overall recommendations for maintaining the generator set.

Service Schedule Details

Maintenance tasks and intervals for fuel, lubrication, and cooling systems.

Air Cleaner, Electrical, Engine & Generator Maintenance

Scheduled maintenance for air intake, electrical, engine, and generator components.

Fuel Filter Service and Bleeding

Instructions for fuel filter service and bleeding the fuel system.

Oil Check and Change Procedures

Instructions for checking and changing the engine oil.

Oil Filter Change Procedure

Procedure for replacing the engine oil filter.

Turbocharger and Mixing Elbow Service

Maintenance for turbocharger inspection and mixing elbow.

Governor Adjustment and Checks

Procedures for checking and adjusting the governor.

Cooling Systems Maintenance

Maintenance guidelines for cooling systems, including strainers and seacocks.

Seawater Pump and Siphon Break Maintenance

Maintenance procedures for seawater pump and siphon break.

Belt Tension Adjustment

Procedures for adjusting belt tension for various belts.

Battery Maintenance and Charging

Guidelines for battery maintenance, including cleaning, charging, and specific gravity checks.

Generator Service and Storage

General generator service requirements and storage procedures.

Troubleshooting Guide

Engine Troubleshooting

Common engine problems and their corrective actions.

Electrical System Troubleshooting

Troubleshooting common issues with the electrical system.

Generator Troubleshooting

Diagnosing and resolving generator output problems.

Wiring Diagrams

Voltage Reconnection Diagrams

Diagrams for reconnecting generator sets for different voltages.

Transfer Switch Wiring Diagrams

Wiring diagrams for various marine transfer switches.

Installation Guide

Installation Introduction and Location

Overview and guidelines for installing the marine generator set, including location selection.

Ventilation and Fuel Systems Installation

Requirements for ventilation, fuel supply, and tank connections.

Cooling and Exhaust Systems Installation

Guidelines for installing cooling systems, strainers, seacocks, and exhaust systems.

Electrical Systems and Battery Installation

Procedures for AC connections, battery installation, and wiring.

Installation Regulations

Governing regulations for generator set installations in vessels.

Wiring and Remote Start Installation

Guidelines for wiring and connecting remote start switches.

Installation Drawings

Generator Selection and Wattage

Wattage Calculation Guidelines

Methods for calculating generator needs based on load types.

Motor Load Calculations

Calculating generator capacity requirements for motor loads.

Lighting and Appliance Load Calculations

Estimating wattage needs for lighting and electrical appliances.

Air Conditioner Wattage Requirements

Typical wattage requirements for marine air conditioners.

Glossary of Abbreviations

Operating Hour Service Log

Kohler 13.5CCOZ Specifications

General IconGeneral
BrandKohler
Model13.5CCOZ
CategoryInverter
LanguageEnglish