TP-6953 7/19118 Section 7 Troubleshooting
7.2 Initial Checks
When troubleshooting, always check for simple
problems first. Check for the following common
problems before replacing parts:
D Loose connections or damaged wiring.
D Discharged or dead battery. Check for a
non-functioning battery charging alternator or battery
charger.
D Fault shutdown. Check for a fault on the controller.
Section 2.6.5 describes the warning faults and
Section 2.6.6 describes the shutdown faults.
D Open circuit breakers. Reset the circuit breaker. If
the c ircuit breaker blows a gain, check the circuit
wiring and components for a cause.
D Incorrect controller settings. Always check the
controller configuration settings before replacing the
controller.
D Controller firmware. Some problems may be
solved by updating the controller’s application
program. Check Tech Tools on the Kohler Power
Resource Center for more information. A personal
computer (laptop) and Kohlerr SiteTe cht software
are required to update the firmware. See the
SiteTecht operation manual for instructions.
7.3 Troubleshooting Chart
Use the following charts to diagnose and correct
common problems. First check for simple causes such
as a dead engine starting battery or an open circuit
breaker. The table groups generator set faults and
suggests likely causes and remedies. The table also
refers you to more detailed information including
sections of this manual, the generator set operation
manual (O/M), the generator set installation manual
(I/M), and the engine service manual (Engine S/M) to
correct the indicated problem.