Residential/Commercial Generator Sets
Models:
14RESA/RESAL
20RESA/RESAL
20RESB
20RESC/RESCL
20RESD
Controllers:
RDC2 Controller
DC2 Controller
TP-6805 8/15b
Service

Table of Contents

Other manuals for Kohler 20RESC

Questions and Answers

  • W
    wagnerangelaAug 14, 2025
    How to troubleshoot inadequate fuel supply in Kohler Portable Generator?
    • M
      Matthew MillerAug 14, 2025
      Check for damaged primary or secondary fuel regulators, loose connections to the fuel solenoid valve, a damaged or closed fuel shutoff valve, an empty LP fuel tank, or other problems with the fuel supply. Check the fuel supply pressure to the generator set.
  • M
    Michael Graham DDSAug 21, 2025
    What to do if the breaker will not close in RUN on my Kohler 20RESC Portable Generator?
    • P
      Phillip KellerAug 21, 2025
      If the breaker won't close in RUN on your Kohler Portable Generator, it could be due to: another breaker being closed (stop the other generator set), auto-discovery not being complete (initiate auto-discovery by ensuring this generator is in RUN mode and the other is stopped with the controller in OFF mode), or bus sensing not being connected correctly (check wiring between both generators and the Automatic Paralleling Module).
  • T
    tnicholsAug 25, 2025
    Why does SiteTech indicate that both engines are under load, but the ATS has not transferred on my Kohler Portable Generator?
    • A
      Antonio Jones MDAug 25, 2025
      If SiteTech indicates that both engines are under load but the ATS hasn't transferred on your Kohler Portable Generator, it could be due to the metering on either generator being backwards. To fix this, select a different model number for the affected generator, then re-select the correct model number. This clears the CT direction flag and allows the generators to re-determine CT direction.
  • A
    Ashley HansonAug 28, 2025
    Why does my Kohler 20RESC Portable Generator experience Main Power Overload Shutdown?
    • R
      russelljoyceAug 28, 2025
      The Main Power Overload Shutdown is caused by an overcurrent condition on the DC power supply circuit. Check the crank, run, and flash relay circuits for short circuits. To address nuisance shutdowns, update the controller firmware to version 6.7 or higher.
  • D
    Dana Owens MDAug 31, 2025
    What to do if my Kohler 20RESC shows a fault shutdown?
    • L
      lori44Aug 31, 2025
      If your Kohler Portable Generator displays a fault shutdown message on the controller, identify and correct the cause of the fault condition. Then, press the OFF button on the controller to clear the fault.
  • E
    Eric LewisSep 3, 2025
    What to do if the thermostat tripped on my Kohler 20RESC?
    • M
      Melanie SpenceSep 3, 2025
      If the thermostat trips on your Kohler Portable Generator, check for blocked air inlets and exhaust outlets. Then, follow the instructions to reset the thermostat.
  • K
    Kimberly PenaSep 6, 2025
    How to fix engine hunting on Kohler Portable Generator models 20RESA(L) and 20RESC(L)?
    • T
      Timothy Moreno IISep 6, 2025
      To address engine hunting in Kohler Portable Generator models 20RESA(L) and 20RESC(L), update to the most current version of firmware available. Also, install vent tubes on the two reference ports on the fuel regulator.
  • J
    Jessica SmithSep 10, 2025
    What to do if my Kohler 20RESC has an Over Crank fault?
    • R
      Rebecca HughesSep 10, 2025
      If your Kohler Portable Generator experiences an Over Crank fault, check the fuel supply, cranking circuit, and cranking battery. You may also need to troubleshoot the engine.
  • C
    Carl CollinsNov 16, 2025
    Why is auto-discovery not completing on my Kohler 20RESC Portable Generator?
    • M
      Michael CarterNov 16, 2025
      Auto-discovery might not complete on your Kohler Portable Generator due to several reasons: * The device may already be auto-discovered to a different contactor. To resolve this, set the engine model number to a different model and then set it back. This action clears any auto-discover information stored in the controller. * The generator or APM circuit breaker might be tripped. Reset the generator circuit breaker or the circuit breaker in the APM. * There might be bad connections between the generator and APM. Correct these connections. * The generator controller might not be seeing bus voltage. Check the wiring between the generator and the APM, paying special attention to the V9 lead connection, as this is the bus sensing. * The other generator is not in OFF. Press the OFF bu...

Kohler 20RESC Specifications

General IconGeneral
Rated Output (Gasoline)20 kW
Rated Output (LPG)18 kW
Voltage120/240 V
Frequency60 Hz
Fuel TypeGasoline, LPG, Natural Gas
Starting SystemElectric
Warranty5 years limited
Dimensions48.5 in L x 29 in H