TP-6811 7/16 31Section 3 Controller
SiteTech Group Notes [
Default Set -
ting
Adjustment
Range *
UnitsParameter
Generator Metering Generator Current L1 A Read Only N/A
Generator Metering Generator Current L2 A Read Only N/A
Generator Metering Generator Current L3 A Read Only N/A
Generator Metering Generator Current Average A Read Only N/A
Generator Metering Generator Frequency Hz Read Only N/A
Genset Info Genset Model Number Select 38RCL, 48RCL,
48RCLA, or
60RCL
(Dropdown list)
Factory set per
unit. See
Section 3.3.2
Genset Info Genset Serial Number 0--20 characters
Genset Info Alternator Part Number 0--20 characters N/A
Genset Info Genset Controller Serial Number 1--10 characters
Genset Info Engine Part Number 0--20 characters N/A
Genset Info Engine Model Number GM 5.0
(Auto select with
genset model)
Genset Info Engine Serial Number 0--10 characters N/A
Genset Info Genset State N/A Read Only
Genset Run Time Genset Controller Clock Time Read Only N/A
Genset Run Time Genset Controller Total
Operation Time
h Read Only N/A
Genset Run Time Engine Total Run Time h Read Only N/A
Genset Run Time Engine Total Run Time Loaded h Read Only N/A
Genset Run Time Engine Total Number Of Starts Read Only N/A
Genset Run Time Genset Date Time Of Last
Maintenance
Read Only
(See Section 2.3.4,
step 6, Reset the
Maintenance Timer
on the RDC2)
1/1/01
12:00:00 AM
Genset Run Time Engine Run T ime Until
Maintenance
h Read Only 200.0
Genset Run Time Genset Controller Date Format MM/DD/YYYY or
DD/MM/YYYY
MM/DD/ YYYY
Genset Run Time Genset Controller Time Format 12 or 24 hr 12 Hr
Genset Run Time Genset Date Time of Next
Maintenance
Read Only N/A
Genset Run Time Maintenance Period In Days days Read Only 365
Genset Run Time Maintenance Period Remaining s Read Only 31536000
Genset Run Time Genset Controller Clock Time
Zone Offset
Read Only 1/1/01
12:00:00 AM
Genset Personality
Profile
ECM Model Auto select with
genset model
DO NOT CHANGE
GM ECM
Genset Personality
Profile
Maximum Alternator Current A Read Only 920
Genset Personality
Profile
Engine Number Of Flywheel
Teeth
Locked 1
Genset Personality
Profile
Engine Warmed Up Temperature _C/F 77 -- 140 _C 32_C(90_F)
See
note in
Section
3.3.2.
Genset Personality
Profile
Engine Cooled Down
Temperature
_C/F Locked 79_C
(174_F)
* Read Only = Not adjustable
w Load management device (LCM, load shed kit, or RXT with combined interface/load management board).
[ Notes indicate applicability to genset or accessories. N/A = Not applicable to the models covered in this manual.
] See TT-1584 for more information about digital inputs and outputs.
Grayed rows are visible in SiteTech but do not apply to all models.