TP-6811 7/1634 Section 3 Controller
SiteTech Group Notes [
Default Set -
ting
Adjustment
Range *
UnitsParameter
Genset System
Configuration
Genset Maximum Percent
Capacity
% 0 -- 120 70.0
Genset System
Configuration
Generator Overloaded Percent % 0 -- 120 85.0
Genset System
Configuration
Under Frequency Shed Level Hz 0--5 0.5
Genset System
Configuration
Base Load Add Time s 10 -- 2400 60
Genset System
Configuration
Base Over Load Shed Time s 2--30 30
Genset System
Configuration
Base Under Frequency Shed
Time
s 1--20 5
Genset System
Configuration
Genset Fuel Type Natural Gas or LP
(pulldown)
Natural Gas
Genset System
Configuration
Automatic Start Minimum
Voltage
V 15 -- 60 51
Genset System
Configuration
Automatic Stop Minimum
Percent Load
% 0 -- 100 20
Genset System
Configuration
Automatic Start Minimum
Voltage Delay
s 1 -- 3600 180
Genset System
Configuration
Automatic Stop Minimum Load
Delay
s 1 -- 3600 180
Genset System
Configuration
ECM Powered Mode On or Off Off
Genset Calibration Genset Calibration Factor
Voltage L1-L2
0.9 -- 1.1 1.0063
Genset Calibration Genset Calibration Factor
Voltage L2-L3
0.9 -- 1.1 0.9909
Genset Calibration Genset Calibration Factor
Voltage L3-L1
0.9 -- 1.1 0.9427
Genset Calibration Genset Calibration Factor
Current L1 -- N
0.9 -- 1.1 1.000000
Genset Calibration Genset Calibration Factor
Current L1
0.9 -- 1.1 1.000000
Genset Calibration Genset Calibration Factor
Current L2
0.9 -- 1.1 1.000000
Genset Calibration Genset Calibration Factor
Current L3
0.9 -- 1.1 1.04
Genset Calibration Current Transformer Calibration
At No Load
0 -- 100 3.5
Genset Calibration Current Transformer Calibration
At Full Load
0 -- 400 121.5
Advanced Speed Control Proportional Gain No effect. N/A
Advanced Speed Control Transient Integral Gain No effect. N/A
Advanced Speed Control Derivative Gain No effect. N/A
Advanced Speed Control Slow Correction Integral Gain No effect. N/A
Advanced Speed Control Diagnostic Derivative Gain No effect. N/A
Advanced Speed Control Diagnostic Transient Integral
Gain
No effect. N/A
Voltage Regulator Voltage Regulator Average
Voltage Adjustment
V 108 -- 660 240.0 (System
voltage)
* Read Only = Not adjustable
w Load management device (LCM, load shed kit, or RXT with combined interface/load management board).
[ Notes indicate applicability to genset or accessories. N/A = Not applicable to the models covered in this manual.
] See TT-1584 for more information about digital inputs and outputs.
Grayed rows are visible in SiteTech but do not apply to all models.