TP-6811 7/1636 Section 3 Controller
SiteTech Group Notes [
Default Set -
ting
Adjustment
Range *
UnitsParameter
Digital Input A1 Digital Input A1 Value Read Only False N/A
Digital Input A1 Digital Input A1 Enabled True or False True N/A
Digital Input A1 Digital Input A1 Event See dropdown list
in SiteTech.
]
Fuel Pressure
Low Warning
N/A
Digital Input A2 Digital Input A2 Value Read Only False N/A
Digital Input A2 Digital Input A2 Enabled True or False True N/A
Digital Input A2 Digital Input A2 Event See dropdown list
in SiteTech.
]
Auxiliary Input
Warning
N/A
Digital Input B1 Digital Input B1 Value Read Only False PIM
Digital Input B1 Digital Input B1 Enabled True or False False PIM
Digital Input B1 Digital Input B1 Event See dropdown list
in SiteTech.
]
None (0) PIM
Digital Input B2 Digital Input B2 Value Read Only False PIM
Digital Input B2 Digital Input B2 Enabled True or False False PIM
Digital Input B2 Digital Input B2 Event See dropdown list
in SiteTech.
]
None (0) PIM
Digital Output A1 Digital Output A1 Value Read Only False N/A
Digital Output A1 Digital Output A1 Event See dropdown list
in SiteTech.
]
NFPA 110
Alarm Active
N/A
Digital Output A2 Digital Output A2 Value Read Only N/A N/A
Digital Output A2 Digital Output A2 Event See dropdown list
in SiteTech.
]
N/A N/A
Digital Output B1 Digital Output B1 Value Read Only False PIM
Digital Output B1 Digital Output B1 Event See dropdown list
in SiteTech.
]
Generator
Running
PIM
Digital Output B2 Digital Output B2 Value Read Only False PIM
Digital Output B2 Digital Output B2 Event See dropdown list
in SiteTech.
]
Common Fault PIM
Digital Output B3 Digital Output B3 Value Read Only False PIM
Digital Output B3 Digital Output B3 Event See dropdown list
in SiteTech.
]
Low Battery
Voltage
Warning
PIM
Digital Output B4 Digital Output B4 Value Read Only False PIM
Digital Output B4 Digital Output B4 Event See dropdown list
in SiteTech.
]
Not In Auto
Warning
PIM
Digital Output B5 Digital Output B5 Value Read Only False PIM
Digital Output B5 Digital Output B5 Event See dropdown list
in SiteTech.
]
Engine Cool
Down Active
PIM
Digital Output B6 Digital Output B6 Value Read Only False PIM
Digital Output B6 Digital Output B6 Event See dropdown list
in SiteTech.
]
Normal Source
Failure
PIM
Digital Output B7 Digital Output B7 Value Read Only False Load
Mgmntw
Digital Output B7 Digital Output B7 Event Read Only 65004 Load
Mgmntw
Digital Output B8 Digital Output B8 Value Read Only False Load
Mgmntw
Digital Output B8 Digital Output B8 Event Read Only 65007 Load
Mgmntw
* Read Only = Not adjustable
w Load management device (LCM, load shed kit, or RXT with combined interface/load management board).
[ Notes indicate applicability to genset or accessories. N/A = Not applicable to the models covered in this manual.
] See TT-1584 for more information about digital inputs and outputs.
Grayed rows are visible in SiteTech but do not apply to all models.