TP-6811 7/1638 Section 3 Controller
SiteTech Group Notes [
Default Set -
ting
Adjustment
Range *
UnitsParameter
Source 1 Calibration Source 1 Calibration Factor
Voltage L3-L1
Read Only 1 RXT
Source 2 System
Configuration
Source 2 System Voltage V 110.0 -- 600.0 240.0 RXT
Source 2 System
Configuration
Source 2 System Frequency Hz 48.0 -- 62.0 60.0 RXT
Source 2 System
Configuration
Source 2 Voltage Debounce
Delay
s 0.1 -- 9.9 0.5 RXT
Source 2 System
Configuration
Source 2 Low Voltage Pickup % 85 -- 100 90 RXT
Source 2 System
Configuration
Source 2 Low Voltage Dropout % 75 -- 98 90 RXT
Source 2 Calibration Source 2 Calibration Factor
Voltage L1-L2
Read Only 1 RXT
Source 2 Calibration Source 2 Calibration Factor
Voltage L2-L3
Read Only 1 RXT
Source 2 Calibration Source 2 Calibration Factor
Voltage L3-L1
Read Only 1 RXT
ATS Exercise Exercise Interval Weekly or
Every Other Week
Weekly RXT
ATS Exercise Exercise Run Duration min 10 -- 30 20 RXT
ATS Exercise Exercise Mode Pulldown
See List
Unloaded
Cycle (2)
RXT
ATS Exercise Exercise Warning Enabled True or False True RXT
ATS Delays ATS Transfer From Preferred
Delay
s 1--10 3 RXT
ATS Delays ATS Transfer From Standby
Delay
s 1 -- 600 120 RXT
ATS Delays ATS Source 2 Engine Start
Delay
s 1--10 3 RXT
Modbus Is Modbus Master 0--1 0
Network Configuration DHCP Enabled True or False True OnCue
Plus
Network Configuration Static IP Address 0.0.0.0 --
255.255.255.255
0.0.0.0 OnCue
Plus
Network Configuration Static Subnet Mask 0.0.0.0 --
255.255.255.255
0.0.0.0 OnCuer
Plus
Network Configuration Static Default Gateway 0.0.0.0 --
255.255.255.255
0.0.0.0 OnCue
Plus
Network Configuration Static DNS Server 1 0.0.0.0 --
255.255.255.255
0.0.0.0 OnCue
Plus
Network Configuration Static DNS Server 2 0.0.0.0 --
255.255.255.255
0.0.0.0 OnCue
Plus
Network Configuration Server Host Name devices.kohler.com devices.kohler.
com
OnCue
Plus
Network Status IP Address Read Only 0.0.0.0 OnCuer
Plus
Network Status Subnet Mask Read Only 0.0.0.0 OnCue
Plus
Network Status Default Gateway Read Only 0.0.0.0 OnCue
Plus
* Read Only = Not adjustable
w Load management device (LCM, load shed kit, or RXT with combined interface/load management board).
[ Notes indicate applicability to genset or accessories. N/A = Not applicable to the models covered in this manual.
] See TT-1584 for more information about digital inputs and outputs.
Grayed rows are visible in SiteTech but do not apply to all models.