TP-6811 7/16 33Section 3 Controller
SiteTech Group Notes [
Default Set -
ting
Adjustment
Range *
UnitsParameter
Genset Personality
Profile
Personality Power Rating 50 Hz
173 346
kW No effect. N/A
Genset Personality
Profile
Personality Power Rating 50 Hz
Delta
kW No effect. N/A
Genset Personality
Profile
Personality Fixed Voltage 60 Hz V No effect. N/A
Genset Personality
Profile
Personality Power Rating Single
Phase60Hz10PF
kW No effect. N/A
Genset Personality
Profile
Personality Power Rating Single
Phase60Hz8PF
kW No effect. N/A
Genset Personality
Profile
Personality Power Rating Fixed
Volt 60 Hz
kW No effect. N/A
Genset Personality
Profile
Personality Power Rating 60 Hz
240 480
kW No effect. N/A
Genset Personality
Profile
Personality Power Rating 60 Hz
230 460
kW No effect. N/A
Genset Personality
Profile
Personality Power Rating 60 Hz
220 440
kW No effect. N/A
Genset Personality
Profile
Personality Power Rating 60 Hz
208 416
kW No effect. N/A
Genset Personality
Profile
Personality Power Rating 60 Hz
190 380
kW No effect. N/A
Genset Personality
Profile
Personality Power Rating 60 Hz
Delta
kW No effect. N/A
Genset Personality
Profile
Personality Installed Options Locked None N/A
Genset System
Configuration
Genset System Voltage V 110 -- 600 240.0
Genset System
Configuration
Genset System Frequency Hz 50/ 60 60.0
Genset System
Configuration
Genset Voltage Phase
Connection
0--3 Single Phase
Genset System
Configuration
Genset Power Rating kW 10-- 5000 48
Genset System
Configuration
Genset Rated Current A Read Only 200
Genset System
Configuration
Genset System Battery Voltage V 12 / 24 12
Genset System
Configuration
Prime Power Application Standby or prime Standby
Genset System
Configuration
Current Transformer Ratio Locked 400 N/A
Genset System
Configuration
Local Start Mode Read Only Off
Genset System
Configuration
Measurement System English or metric English
Genset System
Configuration
ECM Power On or Off Off
Genset System
Configuration
Display Contrast 0 -- 100 50
Genset System
Configuration
Genset System Language No effect. N/A
* Read Only = Not adjustable
w Load management device (LCM, load shed kit, or RXT with combined interface/load management board).
[ Notes indicate applicability to genset or accessories. N/A = Not applicable to the models covered in this manual.
] See TT-1584 for more information about digital inputs and outputs.
Grayed rows are visible in SiteTech but do not apply to all models.